360 Fault tracing
AFE2
Emergency stop (off1
or off3)
Drive has received an
emergency stop (mode
selection Off1 or Off3)
command.
Check that it is safe to continue
operation. Reset the source of the
emergency stop signal (such as an
emergency stop push button). Restart
drive.
If the emergency stop was unintentional,
check the source of the stop signal (for
example,
,
or control word received from an external
control system).
AFE7
Follower
A follower drive has tripped.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
AFEA Enable start signal
missing
(Editable message text)
No enable start signal
received.
Check the setting of (and the source
selected by) parameter
.
AFEB Run enable missing
(Editable message text)
No run enable signal is
received.
Check setting of parameter
. Switch signal on (e.g. in
the fieldbus Control Word) or check
wiring of selected source.
AFEC External power signal
missing
is
voltage is connected to the
XPOW connector of the control
unit.
Check the external 24 V DC power
supply to the control unit, or change the
setting of parameter
.
AFF6
Identification run
Motor ID run will occur at next
start, or is in progress.
Informative warning.
AFF7
Autophasing
Autophasing will occur at next
start.
Informative warning.
B5A0
DIL event
Programmable event:
Drive interlock function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual and description of
parameter
(page
).
B5A2
Power up
Programmable event:
The drive has been powered
up.
Informative event.
B5A4
SW internal
diagnostics
Control unit rebooted
unexpectedly.
Informative event.
B5F6
ID run done
ID run completed.
Informative event.
The auxiliary code specifies the type of
ID run.
0: None
1: Normal
2: Reduced
3: Standstill
B680
SW internal
diagnostics
SW internal malfunction.
Contact your local ABB representative,
quoting the auxiliary code. If the Drive
composer tool is available, also create
and send a ‘support package’ (see Drive
composer manual for instructions).
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...