Parameters 215
Displays the actual present value of on-time timer 2.
The timer runs whenever the signal selected by parameter
When the timer exceeds the limit set by
, bit 1 of
is set to 1. The warning
specified by
is also given if
enabled by
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
0…4294967295 s
Actual present value of on-time timer 2.
-
Sets the warning limit for on-time timer 2.
0 s
0…4294967295 s
Warning limit for on-time timer 2.
-
Configures on-time timer 2.
0000b
0000b…0011b
On-time timer 2 configuration word.
1 = 1
Selects the signal to be monitored by on-time timer 2.
False
Constant 0 (timer disabled).
0
True
Constant 1.
1
RO1
Bit 0 of
(page
2
Source selection (see
on page
).
-
Selects the optional warning message for on-time timer 2.
On-time 2
exceeded
. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
1
Clean device
.
6
Maintain additional
cool fan
7
Maintain cabinet
fan
.
8
Maintain DC
capacitors
9
Maintain motor
bearing
.
10
No.
Name/Value
Description
Def
/
FbEq16
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 1 of
) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 1 of
) switches to 1,
and remains so until
is reset. The warning (if enabled) also stays active until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see
) is given when the limit is reached
2…15
Reserved
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...