Parameters 141
Selects the source of the positive speed enable command.
1 = Positive speed enabled.
0 = Positive speed interpreted as zero speed reference. In the
figure below,
is set to zero after
the positive speed enable signal has cleared.
Actions in different control modes:
Speed control: Speed reference is set to zero and the motor
ramps down along the currently active deceleration ramp. The
drive keeps modulating. The rush controller prevents
additional torque terms from running the motor in the positive
direction.
Torque control: The rush controller monitors the rotation
direction of the motor.
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
Source selection (see
on page
-
Selects the source of the negative speed reference enable
command. See parameter
.
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...