Parameters 243
58.16
Received packets
Shows
the number of message packets received by the drive,
including only such packets that are addressed to the drive.
Note:
The user can reset the counter (by setting the value to
0).
0…65535
No. of message packets.
1 = 1
58.17
Transm packets
Shows the number of message packets sent by the drive.
Note:
The user can reset the counter (by setting the value to
0).
0…65535
No. of message packets.
1 = 1
58.18
All packets
Shows the total number of message packets received by the
drive, including all packets addressed to any valid node on
the fieldbus link.
Note:
The user can reset the counter (by
setting the value to 0).
0…65535
No. of message packets.
1 = 1
58.19
UART errors
Shows the number of messages with communication errors
other than CRC errors which the drive has received (e.g.
UART buffer overflow errors). Read only.
0..65535
No. of messages with errors (excluding messages with CRC
errors).
1 = 1
58.20
CRC errors
Shows the number of messages with Cyclic Redundancy
Check (CRC) errors which the drive has received. Read only.
Note:
High electromagnetic noise levels may generate errors.
0…65535
No. of messages with CRC errors.
1 = 1
58.21
Raw CW LSW
Shows the LSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of the Control word as a hex value.
1 = 1
58.22
Raw CW MSW
Shows the MSW part of the Control Word which the drive
receives from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of the Control word as a hex value.
1 = 1
58.23
Raw SW LSW
Shows the LSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of the Status word as a hex value.
1 = 1
58.24
Raw SW MSW
Shows the MSW part of the Status Word which the drive
sends to the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of the Status word as a hex value.
1 = 1
58.25
Raw Ref 1 LSW
Shows the LSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of reference 1 as a hex value.
1 = 1
58.26
Raw Ref 1 MSW
Shows the MSW part of reference 1 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of reference 1 as a hex value.
1 = 1
58.27
Raw Ref 2 LSW
Shows the LSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 0…15 of reference 2 as a hex value.
1 = 1
58.28
Raw Ref 2 MSW
Shows the MSW part of reference 2 which the drive receives
from the Modbus master. Read only.
0x0000…0xFFFF
Bits 16…32 of reference 2 as a hex value.
1 = 1
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...