228 Parameters
44.19
Val count1 func
Configures value counter 1. This counter measures, by
integration, the area below the signal selected by parameter
. When the total area exceeds the limit
set by parameter
, an alarm is given (if
enabled by bit 1 of this parameter).
The signal is sampled at 1-second intervals. Note that the
scaled (see the “FbEq” column at the signal in question) value
of the signal is used.
The current value of the counter is readable from parameter
. Bit 4 of
that the counter has exceeded the limit.
44.20
Val count1 src
Selects the signal to be monitored by value counter 1. See
parameter
Speed rpm
).
1073742081
Pointer
Value pointer setting (see
on page
-
44.21
Val count1 lim
Sets the alarm limit for value counter 1. See parameter
.
0 … 2147483647
Alarm limit for value counter 1.
1 = 1
44.22
Val count1 div
Divisor for value counter 1. The value of the monitored signal
is divided by this value before integration.
1 … 2147483647
Divisor for value counter 1.
1 = 1
44.23
Val cnt1 alm sel
Selects the alarm for value counter 1. See parameter
.
Value1
Pre-selectable alarm for value counter 1.
0
Mot bearing
Pre-selectable alarm for value counter 1.
1
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...