190 Parameters
27.10
PID fbk ftime
Defines the time constant for the filter through which the
process feedback is connected to the PID controller.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
27.12
PID gain
Defines the gain for the process PID controller. See
parameter
.
0.00 … 100.00
Gain for PID controller.
100 = 1
27.13
PID integ time
Defines the integration time for the process PID controller.
Note:
Setting this value to 0 disables the “I” part, turning the
PID controller into a PD controller.
0.00 … 320.00 s
Integration time.
100 = 1 s
27.14
PID deriv time
Defines the derivation time of the process PID controller. The
derivative component at the controller output is calculated on
basis of two consecutive error values (E
K-1
and E
K
) according
to the following formula:
PID DERIV TIME × (E
K
- E
K-1
)/T
S
, in which
T
S
= 12 ms sample time
E = Error = Process reference - process feedback.
0.00 … 10.00 s
Derivation time.
100 = 1 s
No.
Name/Value
Description
FbEq
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Ti
O
I
G × I
G × I
I = controller input (error)
O = controller output
G = gain
Ti = integration time
Time
Error/Controller output
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...