56 Application macros
PID control macro
The PID control macro is suitable for process control applications, for example
closed-loop pressure, level or flow control systems such as
• pressure boost pumps of municipal water supply systems
• level-controlling pumps of water reservoirs
• pressure boost pumps of district heating systems
• material flow control on a conveyor line.
The process reference signal is connected to analog input AI1 and the process
feedback signal to AI2.
Alternatively, a direct speed reference can be given to the drive through AI1. Then the
PID controller is bypassed and the drive no longer controls the process variable.
Selection between direct speed control and process variable control is done through
digital input DI3.
A constant speed (300 rpm) can be activated through DI4.
Default parameter settings for PID control macro
Below is a listing of default parameter values that differ from those listed in chapter
(page
Parameter
PID control macro
default
No.
Name
C.FALSE
0.000
1500.000
0.000
300 rpm