76 Program features
Thermal motor protection
The motor can be protected against overheating by
• the motor thermal protection model
• measuring the motor temperature with temperature sensors. This will result in a
more accurate motor model.
Thermal motor protection model
The drive calculates the temperature of the motor on the basis of the following
assumptions:
1) When power is applied to the drive for the first time, the motor is at ambient
temperature (defined by parameter
). After this, when power
is applied to the drive, the motor is assumed to be at the estimated temperature.
2) Motor temperature is calculated using the user-adjustable motor thermal time and
motor load curve. The load curve should be adjusted in case the ambient
temperature exceeds 30 °C.
It is possible to adjust the motor temperature supervision limits and select how the
drive reacts when overtemperature is detected.
Note:
The motor thermal model can be used when only one motor is connected to
the inverter.
Temperature measurement
It is possible to detect motor overtemperature by connecting a motor temperature
sensor b24 V and digital input DI6 of the drive, or to optional encoder
interface module FEN-xx.
Constant current is fed through the sensor. The resistance of the sensor increases as
the motor temperature rises over the sensor reference temperature
T
ref
, as does the
voltage over the resistor. The temperature measurement function reads the voltage
and converts it into ohms.
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...