Hardware description
50
Type designation key
The type code of the drive is indicated on its type designation label. The type code
contains information on the specifications and configuration of the drive. The first
digits from left and separated with hyphens express the basic configuration, for
example ACS800-17LC-0250-5. The optional selections are given thereafter,
separated by plus signs, for eL501. For more information refer to,
ACS800-
17LC Ordering information
(3AXD10000006878)
, available on request.
Type code of the basic configuration
* When no options are selected: IP42 (UL Type 1), main switch disconnector (load switch and contactor
in frames R7i+R7i and R8i+R8i or air circuit breaker in frames 2×R8i+2×R8i and up), aR fuses, 230
V AC control voltage, CDP312R Control Panel, EMC filter for 2nd environment (+E200), du/dt limitation
by choke (frames R8i+R8i and up, +E205), common mode filter (+E208), Standard Control Program,
bottom entry and exit of cables, cable lead-through entries, coated boards, CD containing all manuals,
IEC approved components, RDCO-03 module for communication link between the supply and inverter
modules.
Note:
The option codes of the basic configuration are not shown on the type designation
label.
Option codes
Digit
Name/Description
Alternatives
1…6
Product series
ACS800
8…11
Product type
17LC – Cabinet-installed liquid-cooled four-quadrant drive*
13…16 Size
Refer to
the rating tables, page
18
Voltage rating
4 – Voltage range 380…415 V AC
5 – Voltage range 440…500 V AC
7 – Voltage range 525…690 V AC
Class
Code Description
Degree of protection
B055 IP54 (UL Type 12). Not available with +C134.
Construction
C121 Marine construction (reinforced mechanics and fastening, marking of conductors
according to +G341, marine door handles, self extinctive materials)
C129 UL Listed (115 V AC auxiliary voltage, cable conduit entries, all components UL Listed
or Recognized, max. supply voltage 600 V)
C134 CSA Approved (as +C129, with CSA approved components)
C139 Stand alone liquid cooling unit (195 kW)
C140 Single-pump liquid cooling unit (70 kW). The cooling unit will be connected to the line-
up at the factory, pipe connection on the right side, DIN flanges, industrial water.
Control panel CDP312R included on the cubicle door. ACS800-17LC-xxxx-5 units:
External power supply for pump motors is required, refer to oM633, +M634.
C141 Two-pumps liquid cooling unit (195 kW). The cooling unit will be connected to the line-
up at the factory, pipe connection on the right side, DIN flanges, industrial water.
Control panel CDP312R included on the cubicle door. ACS800-17LC-xxxx-5 units:
External power supply for pump motors is required refer to oM633, +M634.
C142 Bottom pipe connection
C144 Pipe connection on the left side of the cabinet. Not available with +C139 and +C140.
C145 ANSI flanges
C146 Sea water heat exchanger
C147 3-way valve for liquid cooling unit in an additional cubicle
Summary of Contents for ACS800-17LC
Page 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Page 4: ......
Page 10: ...Update notice 6 ...
Page 18: ...Table of contents 12 ...
Page 26: ...Safety instructions 20 ...
Page 32: ...Introduction to the manual 26 ...
Page 60: ...Hardware description 54 ...
Page 74: ...Mechanical installation 68 ...
Page 114: ...Electrical installation 108 ...
Page 142: ...Maintenance 136 ...
Page 150: ...Internal cooling circuit 144 ...
Page 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Page 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Page 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...