Technical data
99
Input power connection
Voltage (
U
1
)
208/220/230/240 VAC 3-phase
± 10% for 230 VAC units
380/400/415 VAC 3-phase
± 10% for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase
± 10% for 500 VAC units
525/550/575/600/660/690 VAC 3-phase
± 10% for 690 VAC units
Rated conditional short-
circuit current (IEC 60439-1)
65 kA when protected by fuses given in the fuse tables
Short-circuit current
protection (UL 508C,
CSA C22.2 No. 14-05)
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 100 kA symmetrical amperes (rms) at 600 V maximum when protected by fuses
given in the
fuse table.
Frequency
48 to 63 Hz, maximum rate of change 17%/s
Imbalance
Max.
± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical, U
max
at the field weakening point
Frequency
DTC mode: 0 to 3.2 ·
f
FWP
. Maximum frequency 300 Hz (120 Hz with du/dt or sine filter).
f
FWP
=
f
FWP
: frequency at field weakening point;
U
Nmains
: mains (input power) voltage;
U
Nmotor
: rated motor voltage;
f
Nmotor
: rated motor frequency
Frequency resolution
0.01 Hz
Current
See section
Power limit
1.5 ·
P
hd
, 1.1 ·
P
N
or
P
cont.max
(whichever value is greatest)
Field weakening point
8 to 300 Hz
Switching frequency
3 kHz (average). In 690 V units 2 kHz (average).
Maximum recommended
motor cable length
Type code (EMC equipment)
Max. motor cable length
DTC control
Scalar control
-
300 m (984 ft)
300 m (984 ft)
+E202 *, +E210 *
100 m (328 ft)
100 m (328 ft)
* Motor cable longer than 100 m (328 ft) is allowed but then the EMC Directive requirements may not
be fulfilled.
Efficiency
Approximately 98% at nominal power level
Cooling
Method
Internal fan, flow direction from front to top
Free space around the unit
Refer to
ACS800-04/04M/U4 Cabinet Installation
[68360323 (English)].
Cooling air flow
See
Degrees of protection
IP 00 (UL type: open chassis)
U
Nmains
U
Nmotor
·
f
Nmotor