The ACS800-02/U2
22
Enclosure extension
The extension can be used for accommodating customer equipment; it is also
automatically added whenever required by factory-installed options such as
• switch fuse (always included with the enclosure extension)
• line contactor with Category 0 emergency stop devices (start/stop and emergency
stop switches included)
• thermistor relay(s)
• Pt100 relays
• top cable entry/exit
• additional I/O terminal block.
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (e.g. ACS800-02-
0170-5). The optional selections are given thereafter, separated by + signs (e.g.
+E202). The main selections are described below. Not all selections are available for
all types. For more information, refer to
ACS800 Ordering Information
(EN code:
64556568, available on request).
Type code selections for the ACS800-02
Selection
Alternatives
Product series
ACS800 product series
Type
02
free standing. When no options are selected: 6-pulse diode input bridge, IP 21,
Control Panel CDP312R, no EMC filter, Standard Application Program, no enclosure
extension, cabling from below, boards without coating, one set of manuals.
Size
Refer to
Voltage range
(nominal rating in bold)
2 208/220/
230
/240 VAC
3
380/
400
/415 VAC
5
380/400/415/440/460/480/
500
VAC
+ options
Construction
C111
enclosure extension (bottom entry/exit, switch fuse with gG fuses)
C127
US enclosure extension (US door interlock disconnect switch fuse, US gland/conduit
plate, all components UL/cUL approved)
Resistor braking
D150
brake chopper
Filter
E202
EMC/RFI filter for first environment TN (grounded) system, restricted (the A limits)
E210
EMC/RFI filter for second environment TN/IT (grounded/ungrounded) system
E208
common mode filter
E209
light common mode filter
Line options
(+C111 or
+C127 required)
F250
line contactor
Q951
emergency stop of category 0
F260
ultrarapid line fuses (aR)
Cabinet options
(+C111
+C127 required)
G304
115 VAC auxiliary voltage transformer
Cabling
H351
top entry (+C111+H353 required)
H353
top exit (+C111+H351 required)
H358
US/UK gland/conduit plate
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......