Output ratings
Max. cur-
rent
Input
current
Frame size
ACS580-04-…
Heavy-duty use
Light-duty use
Nominal use
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
hp
A
hp
A
hp
A
A
A
U
n
= 480 V
300
361
400
483
400
505
560
483
R10
505A-4
350
414
450
573
450
585
730
573
R10
585A-4
400
477
500
623
500
650
730
623
R10
650A-4
450
566
600
705
600
725
850
705
R11
725A-4
500
625
700
807
700
820
1020
807
R11
820A-4
500
625
700
807
700
880
1020
807
R11
880A-4
■
UL (NEC) ratings
Output ratings
Max. cur-
rent
Input
current
Frame size
ACS580-04-…
Heavy-duty use
Light-duty use
Nominal use
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
hp
A
hp
A
hp
A
A
A
U
n
= 480 V
300
361
400
483
400
505
560
483
R10
505A-4
350
414
450
573
450
585
730
573
R10
585A-4
400
477
500
623
500
650
730
623
R10
650A-4
450
566
600
705
600
725
850
705
R11
725A-4
500
625
700
807
700
820
1020
807
R11
820A-4
500
625
700
807
700
880
1020
807
R11
880A-4
■
Definitions
Nominal voltage of the drive. For the input voltage range, see section
network specification (page 189)
. 50 Hz for IEC ratings and 60 Hz for UL (NEC) ratings.
U
n
Nominal rms input current at 40 °C (104 °F). Continuous rms input current for dimension-
ing the cables and fuses.
I
1
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed
by drive temperature.
I
max
Continuous rms output current. Available continuously with no over-loading.
I
2
Typical motor power in no-overload use
P
n
Continuous rms output current allowing 10% overload for 1 minute every 10 minutes
when the minimum switching frequency (parameter 97.02) is set to 2 kHz or less. Typical
ratings used for pumps and fans.
I
Ld
Typical motor power for light-overload use (10% overload). The kilowatt ratings apply
to most IEC 4-pole motors. The horsepower ratings apply to most NEMA 4-pole 460 V
motors. Typical ratings used for pumps and fans.
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 10 minutes
I
Hd
** Continuous rms output current allowing 40% overload for 1 minute every 10 minutes
Typical motor power for heavy-duty use
P
Hd
178 Technical data
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...