474 Fieldbus control through a fieldbus adapter
Contents of the fieldbus Control word
The upper case boldface text refers to the states shown in the state diagram (page
.
Bit
Name
Value STATE/Description
0
Off1 control
1
Proceed to
READY TO OPERATE
.
0
Stop along currently active deceleration ramp. Proceed to
OFF1
ACTIVE
; proceed to
READY TO SWITCH ON
unless other interlocks
(OFF2, OFF3) are active.
1
Off2 control
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to a stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON INHIBITED
.
2
Off3 control
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive parameter.
Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
WARNING:
Ensure motor and driven machine can be
stopped using this stop mode.
3
Run
1
Proceed to
OPERATION D
.
Note:
Run enable signal must be active; see drive documentation. If
the drive is set to receive the Run enable signal from the fieldbus, this
bit activates the signal.
0
Inhibit operation. Proceed to
OPERATION INHIBITED
.
4
Ramp out zero
1
Normal operation. Proceed to
RAMP FUNCTION GENERATOR:
OUTPUT D
.
0
Force Ramp function generator output to zero. The drive will
immediately decelerate to zero speed (observing the torque limits).
5
Ramp hold
1
ramp function.
Proceed to
RAMP FUNCTION GENERATOR: ACCELERATOR D
.
0
Halt ramping (Ramp Function Generator output held).
6
Ramp in zero
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0
Force Ramp function generator input to zero.
7
Reset
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON
INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is set as the
source of the reset signal by drive parameters.
0
Continue normal operation.
8
Inching 1
1
Accelerate to inching (jogging) setpoint 1.
Notes:
• Bits 4…6 must be 0.
• See also section
(page
0
Inching (jogging) 1 disabled.
9
Inching 2
1
Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0
Inching (jogging) 2 disabled.
10
Remote cmd
1
Fieldbus control d.
0
Control word and reference not getting through to the drive, except
for bits 0…2.
11
Ext ctrl loc
1
Select External Control Location EXT2. Effective if control location is
parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control location is
parameterized to be selected from fieldbus.
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...