ACS550 User’s Manual
223
Fieldbus adapter
– Parameter 9802
COMM
PROT
SEL
= 4 (
EXT
FBA
).
– The external plug-in fieldbus adapter is configured to use the drive profile
mode or drive profile objects.
The content of the
CONTROL
WORD
depends on the protocol/profile used. See the
user’s manual provided with the FBA module and/or section
on page
Status Word
The
STATUS
WORD
is a 16-bit word containing status information, sent by the drive to
the fieldbus controller. The content of the
STATUS
WORD
depends on the protocol/
profile used. See the user’s manual provided with the FBA module and/or section
ABB Drives profile technical data
.
Reference
The contents of each
REFERENCE
word:
• can be used, as speed or frequency reference
• is a 16-bit word comprised of a sign bit and a 15-bit integer
• Negative references (indicating reversed rotation direction) are indicated by the
two’s complement of the corresponding positive reference value.
The use of a second reference (REF2) is supported only when a protocol is
configured for the ABB Drives profile.
Reference scaling is fieldbus type specific. See the user’s manual provided with the
FBA module and/or the following sections as appropriate:
•
on page
ABB Drives profile technical data
•
on page
Generic profile technical data
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example,
parameters)
can be mapped to Input Words using
parameters
(protocol-dependent, but typically parameters 5104…5126).
Planning
Network planning should address the following questions:
• What types and quantities of devices must be connected to the network?
• What control information must be sent down to the drives?
• What feedback information must be sent from the drives to the controlling
system?
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...