186
ACS550 User’s Manual
8124
ACC IN AUX STOP
Sets the PFC acceleration time for a zero-to-maximum
frequency ramp. This PFC acceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched off.
• Replaces the acceleration ramp defined in
l.
• Applies only until the output of the regulated motor
increases by an amount equal to the output of the
switched off auxiliary motor. Then the acceleration ramp
defined in
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value
entered as the acceleration time.
• A = speed regulated motor accelerating using
parameters (2202 or 2205).
• B = speed regulated motor decelerating using
parameters (2203 or 2206).
• At aux. motor start, speed regulated motor decelerates
using 8125
DEC
IN
AUX
START
.
• At aux. motor stop, speed regulated motor accelerates
using 8124
ACC
IN
AUX
STOP
.
8125
DEC IN AUX START
Sets the PFC deceleration time for a maximum-to-zero
frequency ramp. This PFC deceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched on.
• Replaces the deceleration ramp defined in
.
• Applies only until the output of the regulated motor
decreases by an amount equal to the output of the
auxiliary motor. Then the deceleration ramp defined in
applies.
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value
entered as the deceleration time.
8126
TIMED AUTOCHNG
Sets the autochange using a Timed function. See parameter 8119
AUTOCHNG
LEVEL
.
0 =
NOT
SEL
.
1 =
TIMED
FUNC
1 – Enables autochange when Timed function 1 is active.
2…4 =
TIMED
FUNC
2…4 – Enables autochange when Timed function 2…4 is active.
8127
MOTORS
Sets the actual number of PFC controlled motors (maximum 7 motors, 1 speed regulated, 3 connected direct-on-line
and 3 spare motors).
• This value includes also the speed regulated motor.
• This value must be compatible with the number of relays allocated to PFC if the Autochange function is used.
• If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFC but it needs to be included in this value.
8128
AUX START ORDER
Sets the start order of the auxiliary motors.
1 =
EVEN
RUNTIME
– Time sharing is active. The start order depends on the run times.
2 =
RELAY
ORDER
– The start order is fixed to be the order of the relays.
Code Description
P 8125
P 8124
A
B
1
0
Aux.
motor
f
OUT
t
t
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...