132
ACS550 User’s Manual
2208
EMERG DEC TIME
Sets the deceleration time for maximum frequency to zero for an emergency.
• See parameter 2109
EMERG
STOP
SEL
.
• Ramp is linear.
2209
RAMP INPUT 0
Defines control for forcing the ramp input to 0.
0 =
NOT
SEL
– Not selected.
1 =
DI
1 – Defines digital input
DI
1 as the control for forcing the ramp input to 0.
• Activating the digital input forces ramp input to 0. Ramp output will ramp to 0 according to the currently used ramp
time, after which it will stay at 0.
• De-activating the digital input: ramp resumes normal operation.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for forcing the ramp input to 0.
• See
DI
1 above.
7 =
COMM
– Defines bit 13 of the Command Word 1 as the control for forcing the ramp input to 0.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for forcing the ramp input to 0.
• De-activating the digital input forces ramp input to 0.
• Activating the digital input: ramp resumes normal operation.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for forcing the ramp function
generator input to 0.
• See
DI
1(
INV
) above.
Code Description
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...