ACS550 User’s Manual
105
0305
FAULT WORD 1
Read-only copy of the Fault Word 1.
• When a fault is active, the
corresponding bit for the active fault is
set in the Fault Words.
• Each fault has a dedicated bit
allocated within Fault Words.
• See section
on page
for a description of the faults.
• The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0306
FAULT WORD 2
Read-only copy of the Fault Word 2.
• See parameter 0305.
0307
FAULT WORD 3
Read-only copy of the Fault Word 3.
• See parameter 0305.
0308
ALARM WORD 1
• When an alarm is active, the
corresponding bit for the active alarm
is set in the Alarm Words.
• Each alarm has a dedicated bit
allocated within Alarm Words.
• Bits remain set until the whole alarm
word is reset. (Reset by writing zero to
the word.)
• The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0309
ALARM WORD 2
See parameter 0308.
Code Description
Bit # 0305,
FAULT
WORD
1 0306,
FAULT
WORD
2 0307,
FAULT
WORD
3
0
OVERCURRENT
Obsolete
EFB 1
1
DC OVERVOLT
THERM FAIL
EFB 2
2
DEV OVERTEMP
OPEX LINK
EFB 3
3
SHORT CIRC
OPEX PWR
INCOMPATIBLE SW
4
Reserved CURR
MEAS
USER LOAD CURVE
5
DC UNDERVOLT
SUPPLY PHASE
Reserved
6
AI1 LOSS
ENCODER ERR
Reserved
7
AI2 LOSS
OVERSPEED
Reserved
8 MOT
OVERTEMP Reserved
Reserved
9 PANEL LOSS
DRIVE ID
Reserved
10 ID RUN FAIL
CONFIG FILE
System error
11 MOTOR STALL
SERIAL 1 ERR
System error
12 CB OVERTEMP
EFB CON FILE
System error
13 EXT FAULT 1
FORCE TRIP
System error
14 EXT FAULT 2
MOTOR PHASE
System error
15 EARTH FAULT
OUTP WIRING
Param. setting fault
Bit #
0308,
ALARM
WORD
1
0309,
ALARM
WORD
2
0
OVERCURRENT
OFF BUTTON
1
OVERVOLTAGE
PID SLEEP
2
UNDERVOLTAGE
ID RUN
3
DIRLOCK Reserved
4
COMM LOSS
START ENABLE 1
5
AI1 LOSS
START ENABLE 2
6
AI2 LOSS
EMERGENCY STOP
7
PANEL LOSS
ENCODER ERROR
8
DEVICE OVERTEMP
FIRST START
9
MOTOR TEMP
Reserved
10 Reserved
USER LOAD CURVE
11
MOTOR STALL
START DELAY
12 AUTORESET Reserved
13 PFC AUTOCHANGE
Reserved
14 PFC ILOCK
Reserved
15 Reserved
Reserved
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...