WARNING! 

To disconnect the internal EMC 

filter, remove the screws marked with “

-

”, or 

replace the screws marked with “ ” with the 
provided polyamide screws, depending on 
the frame size.

Power connections

Optional braking

Wiring the controls

 1. Strip control cable 

sheathing and twist the 
copper shield into a 
bundle. 

 2. Route control cable(s) 

through clamp(s) and 
tighten clamp(s).

 3. Connect the ground 

shield bundle for digital 
and analog I/O cables at 
X1-1. (Ground only at 
the drive end.)

 4. Strip the individual 

control wires and connect to the drive terminals. 
Use a tightening torque of 0.4 N·m (0.3 lb·ft). See 

Control connections

 below or, for more detail, 

see 

User’s Manual

.

Control connections

Note 1. 

Jumper setting (two switch types possible):

Note 2. 

Code: 0 = open, 1 = connected

WARNING!

 The maximum voltage for digital 

inputs is 30 V.

Check installation

Before applying power, perform the following 
checks. 

Reinstall the cover

 1. Align the cover 

and slide it on.

 2. Tighten the captive 

screws around the 
edge of the cover.

 3. Slide the hood 

down over the top 
of the cover (UL 
type 12 only).

 4. Install the two 

screws that attach 
the hood (UL type 
12 only).

 5. Install the control panel.

Note:

  The control panel window must be closed to 

comply with IP54 / UL type 12.

 6. Optional: Add a lock (not supplied) to secure 

the control panel window.

Apply power

Always reinstall the front cover before turning 
power on. 

WARNING!

 The ACS550 will start up 

automatically at power up, if the external run 
command is on.

 1. Apply input power.

When power is applied to the ACS550, the 
green LED comes on.

Note:

  Before increasing motor speed, check that 

the motor is running in the desired direction.

Start-up

In start-up, enter motor data (collected earlier) 
and, if needed, edit parameters that define how 
the drive operates and communicates.

Assistant Control Panel

The Start-up Assistant steps through typical 
start-up selections, and runs automatically 
upon the initial power up. At other times, use 
the steps below to run the Start-up Assistant.

 1. Use the MENU key to 

access the Main menu.

 2. Select ASSISTANTS.
 3. Select Start-up Assistant.
 4. Follow the screen 

instructions to configure the 
system. 

Note:

For common parameters and menu items, 
use the Help key

 

 

to display 

descriptions.
If you encounter alarms or faults, 
use the Help key or refer to chapter 

Diagnostics

 in 

User’s Manual

.

Basic Control Panel

The Basic Control Panel does not 
include the Start-up Assistant. Refer to 
section 

How to start up the drive

 in 

User’s Manual

 and manually enter any 

parameter changes desired.

System type

R1...R3

R4

R5...R6

EM1 EM3 EM1 EM3 F1 F2

IT system

-

-

- -

Corner grounded TN 

system

-

X0033

GND

Power output to motor

EM3

PE

(U2, V2, W2)

Power input

(U1, V1, W1)

EM1

Frame size R1…R4

See table Optional 

braking below.

X0035

Power output to motor

PE

(U2, V2, W2)

GND

Power input

F1

(U1, V1, W1)

F2

Frame size R5

See table Optional 

braking below.

Power output to motor

PE

(U2, V2, W2)

GND

Power input

(U1, V1, W1)

X0013

F2

F1

Frame size R6

See table Optional 

braking below.

Frame size

Terminal labels

Brake options

R1, R2

BRK+, BRK-

Brake resistor

R3…R6

UDC+, UDC-

• Braking unit 
• Chopper and resistor

IP5005

2

3, 4

1

SCR

2

AI1

3

AGND

4

10V

5

AI2

6

AGND

7

AO1

8

AO2

9

AGND

X1

Ext. freq. ref. 1:

 0…10 V

Output freq.:

 0…20 mA

Output current:

 0…20 mA

Analog input com. 

Not used

Analog output com. 

Analog input com. 

Ref. voltage 10 V DC

ABB Standard macro

Signal cable shield (screen)

10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6

19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B

Start/Stop:

 Active = start

Fwd/Rev:

 Active = rev. dir.

Constant speed sel.

2

Constant speed sel.

2

Ramp pair:

 Active = 2

nd

 ramp pair

Not used

Aux. volt. common
Digital input com. for all

Aux. volt. 24 V DC

Relay output 1
Default operation: 

Relay output 2
Default operation: 

Relay output 3
Default operation: 

Ready

 = 19/21 connected 

Running

 = 22/24 connected 

Fault(-1)

 =25/27 connected

(Fault => 25/26 connected) 

J1

AI1: 0…10 V
AI2: 0(4)…20 mA

ON

ON

ON

12

or

J1

DI3

DI4

Output

0

0

Reference through AI1

1

0

CONSTANT

 

SPEED

 1 (1202)

0

1

CONSTANT

 

SPEED

 2 (1203)

1

1

CONSTANT

 

SPEED

 3 (1204)

Check

Environment conforms to specifications.

The drive is mounted securely.

Proper cooling space around the drive.

Motor and driven equipment are ready for start.

For IT systems and corner grounded TN systems: 

The internal EMC filter is disconnected (see the table 

in 

Wiring power

).

Drive is properly grounded.

Input power (mains) voltage matches the drive 

nominal input voltage.

The input power (mains) terminals, U1, V1, W1, are 

connected and tightened as specified.

The input power (mains) fuses are installed.

The motor terminals, U2, V2, W2, are connected and 

tightened as specified.

Motor cable is routed away from other cables.

NO power factor compensation capacitors are in the 

motor cable.

Control terminals are wired and tightened as 

specified.

NO tools or foreign objects (such as drill shavings) 

are inside the drive.

NO alternate power source for the motor is 

connected – no input voltage is applied to the output 

of the drive.

2

1

4

3

5

6

FM

LOC

DIR

12:45

MENU

400RPM

1200 RPM

12.4 A

405 dm3/s

                     
             
             
             

5 A

1 Hz

7 %

10

.

0

.

49

.

49.1H

z

LOC

DIR

MENU

00:00

?

C

ode

: 3AU

A

000

0005

428

 REV E /

 EN

Ef

fe

ctiv

e: 2

009

-07-07

Sup

ersed

es:

 200

7-04-1

6

Reviews: