224
ACS510 User’s Manual
Technical Data
example of an effective construction (for example Ölflex-Servo-FD 780 CP,
Lappkabel or MCCMK, NK Cables).
EN 61800-3 Compliant Motor Cables
To comply with EN 61800-3
requirements:
• Motor cables must have an effective screen as described in "Effective Motor
• Motor cable screen wires must be twisted together into a bundle (the bundle
length must be less than five times its width) and connected it to the terminal
marked
(at the bottom right-hand corner of the drive).
• Motor cables must be grounded, at the motor end, with an EMC cable gland. The
ground must contact the cable screen all the way around the cable.
• For EN 61800-3 First Environment, Restricted Distribution (CISPR11 Class A),
and EN 61800-3 Second Environment compliance, the drive includes an internal
filter that provides compliance for at least 30 m (100 ft.) motor cable lengths. For
some drives, longer cable lengths require an additional, external RFI/EMC filter
as specified in the table below. The RFI/EMC filters are separate options and
installation must conform to the instructions in the filter package for all cable
screen connections.
Insulation Jacket
Braided Metallic Screen
Inner Insulator
L1
L2
L3