306 Actual signals and parameters
DLY & AI1 L1
State change when delay time defined by parameter
has elapsed and AI1 value < par.
value.
69
COMM VAL1
#0
bit 0. 1 = state change.
70
COMM VAL1
#1
bit 1. 1 = state change.
71
COMM VAL1
#2
bit 2. 1 = state change.
72
COMM VAL1
#3
bit 3. 1 = state change.
73
COMM VAL1
#4
bit 4. 1 = state change.
74
COMM VAL1
#5
bit 5. 1 = state change.
75
COMM VAL1
#6
bit 6. 1 = state change.
76
COMM VAL1
#7
bit 7. 1 = state change.
77
AI2H2DI4SV1O State change according to supervision parameters
when AI2 value > par.
value and DI4 is active.
78
AI2H2DI5SV1O State change according to supervision parameters
when AI2 value > par.
value and DI5 is active.
79
STO
State change when STO (Safe torque off) has been
triggered.
80
STO(-1)
State change when STO (Safe torque off) becomes inactive
and the drive operates normally.
81
8426 ST1 TRIG TO
ST N
Selects the source for the trigger signal which changes the
state from state 1 to state N. State N is defined with
parameter
Note:
State change to state N (
has a higher priority than state change to the next state
(
).
See parameter
8427 ST1 STATE N
Defines the state N. See parameter
.
STATE 1
State 1
1
STATE 2
State 2
2
STATE 3
State 3
3
STATE 4
State 4
4
STATE 5
State 5
5
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...