![ABB ACS355 series User Manual Download Page 269](http://html.mh-extra.com/html/abb/acs355-series/acs355-series_user-manual_2968269.webp)
Actual signals and parameters 269
DI3
Digital input DI3. Used when parameter
value is set to
5
DI4
Digital input DI4. Used when parameter
value is set to
6
DI5
Digital input DI5. Used when parameter
value is set to
7
3503 ALARM LIMIT
Defines the alarm limit for motor temperature measurement.
Alarm
) indication is given when the
limit is exceeded. When parameter
value is set to
/
: 1 = alarm.
0
x…x
Alarm limit
-
3504 FAULT LIMIT
Defines the fault trip limit for motor temperature
measurement. The drive trips on fault
) when the limit is exceeded. When parameter
value is set to
: 1 =
fault.
0
x…x
Fault limit
-
3505 AO
EXCITATION
Enables current feed from analog output AO. Parameter
setting overrides parameter group
settings.
With PTC the output current is 1.6 mA.
With Pt 100 the output current is 9.1 mA.
DISABLE
Disabled
0
ENABLE
Enabled
1
36 TIMED
FUNCTIONS
Time periods 1 to 4 and booster signal. See section
time clock and timed functions
on page
.
3601 TIMERS
ENABLE
Selects the source for the timed function enable signal.
NOT SEL
Timed function is not selected.
0
DI1
Digital input DI. Timed function enable on the rising edge of
DI1.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
ACTIVE
Timed function is always enabled.
7
DI1(INV)
Inverted digital input DI1. Timed function enable on the
falling edge of DI1.
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...