250 Actual signals and parameters
3005 MOT THERM
PROT
Selects how the drive reacts when the motor
overtemperature is detected.
NOT SEL
Protection is inactive.
0
FAULT
The drive trips on fault
) when the
temperature exceeds 110 °C, and the motor coasts to stop.
1
ALARM
) when the
motor temperature exceeds 90 °C.
2
3006 MOT THERM
TIME
Defines the thermal time constant for the motor thermal
model, ie, the time within which the motor temperature has
reached 63% of the nominal temperature with steady load.
For thermal protection according to UL requirements for
NEMA class motors, use the rule of thumb: Motor thermal
time = 35 · t6. t6 (in seconds) is specified by the motor
manufacturer as the time the motor can safely operate at six
times its rated current.
Thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip curve 700 s, and for a Class 30 trip curve 1050 s.
500 s
256…9999 s
Time constant
1 = 1 s
All parameters
No.
Name/Value
Description
Def/FbEq
}
Motor load
Temp. rise
100%
63%
Par.
t
t
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...