Actual signals and parameters 247
2626 SPD EST BW
TRIM
Speed estimation bandwidth trimming.
Effective only in vector:speed and vector:torque modes.
Speed estimation is trimmed to be very dynamic. When the
drive is used with non-dynamic loads such as compressors,
pumps and fans, this variable can be trimmed to a higher
value.
0%
0…20%
Speed estimation bandwidth
1 = 1%
29 MAINTENANCE
TRIG
Maintenance triggers
2901 COOLING FAN
TRIG
Defines the trigger point for the drive cooling fan run time
counter. Value is compared to parameter
value.
0.0 kh
0.0…6553.5 kh Time. If parameter value is set to zero, the trigger is
disabled.
1 = 0.1 kh
2902 COOLING FAN
ACT
Defines the actual value for the cooling fan run time counter.
When parameter
has been set
to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by
parameter
, a maintenance notice is displayed on the
panel.
0.0 kh
0.0…6553.5 kh Time. Parameter is reset by setting it to zero.
1 = 0.1 kh
2903 REVOLUTION
TRIG
Defines the trigger point for the motor revolution counter.
Value is compared to parameter
value.
0 Mrev
0…65535 Mrev Millions of revolutions. If parameter value is set to zero, the
trigger is disabled.
1 =
1 Mrev
2904 REVOLUTION
ACT
Defines the actual value for the motor revolution counter.
When parameter
has been set to
a non zero value, the counter starts. When the actual value
of the counter exceeds the value defined by parameter
, a maintenance notice is displayed on the panel.
0 Mrev
0…65535 Mrev Millions of revolutions. Parameter is reset by setting it to
zero.
1 =
1 Mrev
2905 RUN TIME
TRIG
Defines the trigger point for the drive run time counter. Value
is compared to parameter
value.
0.0 kh
0.0…6553.5 kh Time. If parameter value is set to zero, the trigger is
disabled.
1 = 0.1 kh
2906 RUN TIME
ACT
Defines the actual value for the drive run time counter.
When parameter
has been set to a
non zero value, the counter starts. When the actual value of
the counter exceeds the value defined by parameter
, a
maintenance notice is displayed on the panel.
0.0 kh
0.0…6553.5 kh Time. Parameter is reset by setting it to zero.
1 = 0.1 kh
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...