Actual signals and parameters 19
NOT SEL
User parameter set change is not possible through a digital
input. Parameter sets can be changed only from the control
panel.
0
DI1
User parameter set control through digital input DI1. Falling
edge of digital input DI1: User parameter set 1 is loaded into
use. Rising edge of digital input DI1: User parameter set 2 is
loaded into use.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1,2
User parameter set selection through digital inputs DI1 and
DI2. 1 = DI active, 0 = DI inactive.
7
DI2,3
See selection
.
8
DI3,4
See selection
.
9
DI4,5
See selection
.
10
DI1,2,3
User parameter set selection through digital inputs DI1, DI2
and DI3. 1 = DI active, 0 = DI inactive.
12
DI2,3,4
See selection
,3.
13
DI3,4,5
See selection
,3.
14
DI1(INV)
User parameter set control through inverted digital input
DI1. Falling edge of inverted digital input DI1: User
parameter set 2 is loaded into use. Rising edge of inverted
digital input DI1: User parameter set 1 is loaded into use.
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
DI4(INV)
See selection
.
-4
All parameters
No.
Name/Value
Description
Def/FbEq
DI1
DI2 User parameter set
0
0
User parameter set 1
1
0
User parameter set 2
0
1
User parameter set 3
1
1
User parameter set 4
DI1
DI2
DI3 User parameter set
0
0
0
User parameter set 1
1
0
0
User parameter set 2
0
1
0
User parameter set 3
1
1
0
User parameter set 4
0
0
1
User parameter set 5
1
0
1
User parameter set 6
x
1
1
No reaction