Related documents

 3AXD50000622467 Rev A EN 2020-04-21 

© Copyright 2020 ABB. All rights reserved.

ACS355 user’s manual

3AUA0000066143

ACS355 manual list

9AKK107680A5563

Configure fieldbus communication (optional)

See the drive user’s manual.

ENTRY OF START-UP DATA (parameter group 99)

If you have an assistant control panel, select the 

language. See parameter 

9901 for the values of 

the available language alternatives.

Select the motor type (

9903). 

1 (

AM): Asynchronous motor

2 (

PMSM): Permanent magnet synchronous 

motor.

Setting of parameter 

9903 is shown below as an 

example of parameter setting with the basic 

control panel.
1. To go to the Main menu, press 

 if the 

bottom line shows OUTPUT; otherwise press 

 repeatedly until you see MENU at the 

bottom.

 

2. Press keys 

/

 until you see “PAr”.

 

3. Press 

. Panel changes to Parameter 

mode.The display shows the number of one of 

the parameter groups.

4.Find the appropriate parameter group (

99) 

with keys 

/

.

 

5.Press 

. The display shows one of the 

parameters in the selected group. Find the 

appropriate parameter (

9903) with keys 

/

.

 

6.Press and hold 

 for about two seconds 

until parameter value is shown with 

SET

 under 

the value. If necessary, change the value with 

keys /

 

.

7. Save the parameter value by pressing 

.

 

Select the application macro (

9902) according 

to how the control cables are connected. 

The default value 1 (

ABB STANDARD) is suitable 

in most cases.

 

Select the motor control mode (

9904).

1 (

VECTOR: SPEED) suits most cases

2 (

VECTOR: TORQ) suits torque control

3 (

SCALAR: FREQ) suits if control accuracy is not 

important, and for certain special cases. See 

user’s manual. Not for permanent magnet 

synchronous

 

motors.

Enter the motor data from the motor 

nameplate: motor nominal voltage (

9905), 

nominal motor current

 

(

9906), motor nominal 

frequency (

9907), motor nominal speed (9908), 

motor nominal power (

9909)

Select the motor identification method (

9910).

The default value 0 (

OFF/IDMAGN) using the 

identification magnetization is suitable for 

most applications. It is applied here. (Requires 

also that 

9904 is set to 1 (VECTOR: SPEED) or 

2 (

VECTOR: TORQ)).

IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (

OFF/IDMAGN)

Press key 

 to switch to local control (LOC 

shown on the left).

Press 

 to start the drive. The motor model 

is now calculated by magnetizing the motor for 

10 to 15 s at zero speed.

DIRECTION OF THE MOTOR ROTATION

Check the direction of the motor rotation.

 

1. If the drive is in remote control (REM shown 

on the left), switch to local control by pressing 

.

 

2. To go to the Main menu, press 

 if the 

bottom line shows OUTPUT; otherwise press 

 repeatedly until you see MENU at the 

bottom.

3. Press keys 

/

 until you see “rEF” 

and press 

.

4.Increase the frequency reference from zero to 

a small value with key 

5.Press 

 to start the motor.

6.Check that the actual direction of the motor is 

the same as indicated on the display (FWD 

means forward and REV reverse).

7. Press 

 to stop the motor.

To change the forward and reverse rotation 

directions (with a parameter):
Invert the phases by changing the value of 

parameter 

9914 to the opposite, ie, from 0 (NO) 

to 1 (

YES), or vice versa.

Verify your work by repeating the rotation 

direction check as described above.

 

SPEED LIMITS AND ACCELERATION/DECELERATION TIMES

Set the minimum speed (

2001), maximum speed 

(

2002), acceleration time 1 (2202), and 

deceleration time 1 (

2203)

 

SAVING A USER MACRO AND FINAL CHECK

The start-up is now completed. If you want to 

save your setting as a user macro, scroll to 

Parameter 9902 and select value USER S1 SAVE.

 

Check that there are no faults or alarms shown 

on the display.

The drive is now ready for use.

 

 

9901 LANGUAGE

 

 

CANCEL

SAVE

00:00

PAR EDIT

[0]

ENGLISH

REM

REM

PAR

    FWD

9903

REM

MENU

    FWD

rEF

 

REM

MENU

    FWD

PAr

 

REM

PAR

    FWD

-01-

 

REM

PAR

    FWD

-99-

 

REM

PAR

    FWD

9903

 

REM

PAR 

SET

   FWD

01

 

REM

PAR

    FWD

9903

 

REM

PAR

    FWD

9902

 

REM

PAR

    FWD

9904

 

REM

PAR

    FWD

9910

 

LOC

REM

LOC

PAR

    FWD

9910

 

LOC

REM

LOC

PAR

    FWD

9910

 

LOC

MENU

    FWD

PAr

 

LOC

Hz

SET

  FWD

xxx

.

forward

reverse

LOC

PAR

    FWD

9914

 

LOC

PAR

    FWD

2001

 

LOC

PAR

    FWD

9902

 

Fault codes

This is a short list of fault messages. 

Ratings    

Fuses and typical power cable sizes

The table list the fuses for protection against short-circuits in the input power 

cable or drive. The table also shows typical power cable sizes.  

Ambient conditions

Fault

Description

0001

OVERCURRENT - Output current has exceeded trip level.

0002

DC OVERVOLT - Excessive intermediate circuit DC voltage.

0003

DEV OVERTEMP - Drive IGBT temperature is excessive.

0004

SHORT CIRC - Short-circuit in motor cable(s) or motor.

0006

DC UNDERVOLT - Intermediate circuit DC voltage is not sufficient.

0009

MOT OVERTEMP - Motor temperature estimation is too high.

0016

EARTH FAULT - Drive has detected earth (ground) fault in motor or motor cable.

0022

SUPPLY PHASE - Intermediate circuit DC voltage is oscillating due to missing 

input power line phase or blown fuse.

0044

SAFE TORQUE OFF - STO (Safe torque off) requested via STO terminal and it 

functions correctly. Parameter 3025 STO OPERATION is set to react with fault.

ACS355-…

x = E/U

Input

Input with 

choke

 Output

Frame

size

I

1N

I

1N 

(480 V)

I

1N

I

1N 

(480 V)

I

2N

I

2,1/10

I

2max

P

N

A

A

A

A

A

A

A

kW

hp

1-phase 

U

N

 = 230 V (200…240 V)

01x-02A4-2

6.1

-

4.5

-

2.4

3.6

4.2

0.37

0.5

R0

01x-04A7-2

11

-

8.1

-

4.7

7.1

8.2

0.75

1

R1

01x-06A7-2

16

-

11

-

6.7

10.1

11.7

1.1

1.5

R1

01x-07A5-2

17

-

12

-

7.5

11.3

13.1

1.5

2

R2

01x-09A8-2

21

-

15

-

9.8

14.7

17.2

2.2

3

R2

3-phase 

U

N

 = 230 V (200…240 V)

03x-02A4-2

4.3

-

2.2

-

2.4

3.6

4.2

0.37

0.5

R0

03x-03A5-2

6.1

-

3.5

-

3.5

5.3

6.1

0.55

0.75

R0

03x-04A7-2

7.6

-

4.2

-

4.7

7.1

8.2

0.75

1

R1

03x-06A7-2

12

-

6.1

-

6.7

10.1

11.7

1.1

1.5

R1

03x-07A5-2

12

-

6.9

-

7.5

11.3

13.1

1.5

2

R1

03x-09A8-2

14

-

9.2

-

9.8

14.7

17.2

2.2

3

R2

03x-13A3-2

22

-

13

-

13.3

20.0

23.3

3

3

R2

03x-17A6-2

25

-

14

-

17.6

26.4

30.8

4

5

R2

03x-24A4-2

41

-

21

-

24.4

36.6

42.7

5.5

7.5

R3

03x-31A0-2

50

-

26

-

31

46.5

54.3

7.5

10

R4

03x-46A2-2

69

-

41

-

46.2

69.3

80.9

11.0

15

R4

3-phase 

U

N

 = 400/480 V (380…480 V)

03x-01A2-4

2.2

1.8

1.1

0.9

1.2

1.8

2.1

0.37

0.5

R0

03x-01A9-4

3.6

3.0

1.8

1.5

1.9

2.9

3.3

0.55

0.75

R0

03x-02A4-4

4.1

3.4

2.3

1.9

2.4

3.6

4.2

0.75

1

R1

03x-03A3-4

6.0

5.0

3.1

2.6

3.3

5.0

5.8

1.1

1.5

R1

03x-04A1-4

6.9

5.8

3.5

2.9

4.1

6.2

7.2

1.5

2

R1

03x-05A6-4

9.6

8.0

4.8

4.0

5.6

8.4

9.8

2.2

3

R1

03x-07A3-4

12

9.7

6.1

5.1

7.3

11.0

12.8

3

3

R1

03x-08A8-4

14

11

7.7

6.4

8.8

13.2

15.4

4

5

R1

03x-12A5-4

19

16

11

9.5

12.5

18.8

21.9

5.5

7.5

R3

03x-15A6-4

22

18

12

10

15.6

23.4

27.3

7.5

10

R3

03x-23A1-4

31

26

18

15

23.1

34.7

40.4

11

15

R3

03x-31A0-4

52

43

25

20

31

46.5

54.3

15

20

R4

03x-38A0-4

61

51

32

26

38

57

66.5

18.5

25

R4

03x-44A0-4

67

56

38

32

44

66

77.0

22.0

30

R4

3AXD00000353783 L

I

1N

continuous rms input current (for dimensioning cables and fuses)

I

1N

 (480 V) continuous rms input current (for dimensioning cables and fuses) for drives with 

480 V input voltage

I

2N

continuous rms current. 50% overload is allowed for one minute every ten 

minutes.

I

2,1/10

maximum (50% overload) current allowed for one minute every ten minutes

I

2max

maximum output current. Available for two seconds at start, otherwise as long 

as allowed by the drive temperature.

P

N

typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The 

horsepower ratings apply to most NEMA 4-pole motors. 

ACS355-…

x = E/U

Fuses

Size of copper conductor

gG

UL 

Class T 

or CC

 

(600 V)

Supply

(U1, V1, W1)

Motor

(U2, V2, W2)

PE

Brake

(BRK+, BRK-)

A

A

mm

2

AWG mm

2

AWG mm

2

AWG mm

2

AWG

1-phase 

U

N

 = 230 V (200…240 V)

01x-02A4-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

01x-04A7-2

16

20

2.5

14

0.75

18

2.5

14

2.5

14

01x-06A7-2

16/20

1)

25

2.5

10

1.5

14

2.5

10

2.5

12

01x-07A5-2

20/25

1)

30

2.5

10

1.5

14

2.5

10

2.5

12

01x-09A8-2

25/35

1)

35

6

10

2.5

12

6

10

6

12

3-phase 

U

N

 = 230 V (200…240 V)

03x-02A4-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-03A5-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-04A7-2

10

15

2.5

14

0.75

18

2.5

14

2.5

14

03x-06A7-2

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-07A5-2

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-09A8-2

16

20

2.5

12

2.5

12

2.5

12

2.5

12

03x-13A3-2

25

30

6

10

6

10

6

10

2.5

12

03x-17A6-2

25

35

6

10

6

10

6

10

2.5

12

03x-24A4-2

63

60

10

8

10

8

10

8

6

10

03x-31A0-2

80

80

16

6

16

6

16

6

10

8

03x-46A2-2

100

100

25

2

25

2

16

4

10

8

3-phase 

U

N

 = 400/480 V (380…480 V)

03x-01A2-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-01A9-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-02A4-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-03A3-4

10

10

2.5

12

0.75

18

2.5

12

2.5

12

03x-04A1-4

16

15

2.5

12

0.75

18

2.5

12

2.5

12

03x-05A6-4

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-07A3-4

16

20

2.5

12

1.5

14

2.5

12

2.5

12

03x-08A8-4

20

25

2.5

12

2.5

12

2.5

12

2.5

12

03x-12A5-4

25

30

6

10

6

10

6

10

2.5

12

03x-15A6-4

35

35

6

8

6

8

6

8

2.5

12

03x-23A1-4

50

50

10

8

10

8

10

8

6

10

03x-31A0-4

80

80

16

6

16

6

16

6

10

8

03x-38A0-4

100

100

16

4

16

4

16

4

10

8

03x-44A0-4

100

100

25

4

25

4

16

4

10

8

3AXD00000353783 L

1)

 If 50% overload capacity is needed, use the larger fuse alternative.

Requirement

During operation (installed for stationary use)

Installation altitude

0…2000 m (0…6562 ft) above sea level (with output derating 

above 1000 m [3281 ft])

Surrounding air 

temperature

-10…+50 °C (14…122 °F). If the temperature is more than 40 °C 

(104 °F), output derating is necessary. No frost permitted.

Relative humidity

0…95% without condensation

Dimensions and weights

Free space requirements

Markings

The applicable markings are shown on the type designation label.

Declaration of conformity

The drive is equipped with a Safe torque off function (STO). If you implement, 

start up, use or maintain a system that uses the STO, read and obey the STO 

instructions in the drive user’s manual.

Contamination levels

(IEC 60721-3-3: 2002)

No conductive dust permitted

Shock (IEC 60068-2-27, 

ISTA 1A)

Not permitted

Free fall

Not permitted

IP20 (cabinet) / UL open

Frame 

size

H1

H2

H3

W

D

Weight

mm

in

mm

in

mm

in

mm

in

mm

in

kg

lb

R0

169

6.65

202

7.95

239

9.41

70

2.76

161 6.34

1.2

2.6

R1

169

6.65

202

7.95

239

9.41

70

2.76

161 6.34

1.4

3.0

R2

169

6.65

202

7.95

239

9.41

105

4.13

165 6.50

1.8

3.9

R3

169

6.65

202

7.95

236

9.29

169

6.65

169 6.65

3.1

6.9

R4

181

7.13

202

7.95

244

9.61

260 10.24 169 6.65

5.2

11.5

IP20 / NEMA 1

Frame 

size

H4

H5

W

D

-

Weight

mm

in

mm

in

mm

in

mm

in

-

-

kg

lb

R0

257 10.12 280 11.02

70

2.76

169

6.65

-

-

1.6

3.5

R1

257 10.12 280 11.02

70

2.76

169

6.65

-

-

1.8

3.9

R2

257 10.12 282 11.10 105

4.13

169

6.65

-

-

2.2

4.8

R3

260 10.24 299 11.77

169

6.65

177

6.97

-

-

3.7

8.2

R4

270 10.63 320 12.60 260 10.24 177

6.97

-

-

5.8

12.9

3AXD00000353783 L

IP20 (cabinet) / UL open

H1

height without fastenings or clamping plate

H2

height with fastening and without clamping plate

H3

height with fastenings and clamping plate

W

width

D

depth

IP20 / NEMA 1 (drive with optional MUL-xx kit installed)

H4 height with fastenings and connection box
H5

height with fastenings, connection box and hood

Above

Below

Sides

mm

in

mm

in

mm

in

75

3

75

3

0

0

3AXD00000353783 L

CE

UL RCM EAC

WEEE EIP

TÜV 

Nord 

Requirement

During operation (installed for stationary use)

„