Actual signals and parameters
228
84 SEQUENCE PROG
Sequence programming. See section
on page
8401
SEQ PROG ENABLE
Enables sequence programming.
If sequence programming enable signal is lost, the sequence programming is
stopped, sequence programming state (
SEQ PROG STATE) is set to 1
and all timers and outputs (RO/TO/AO) are set to zero.
DISABLED
DISABLED
Disabled
0
EXT2
Enabled in external control location 2 (EXT2)
1
EXT1
Enabled in external control location 1 (EXT1)
2
EXT1&EXT2
Enabled in external control locations 1 and 2 (EXT1 and EXT2)
3
ALWAYS
Enabled in external control locations 1 and 2 (EXT1 and EXT2) and in local
control (LOCAL)
4
8402
SEQ PROG START
Selects the source for the sequence programming activation signal.
When sequence programming is activated, the programming starts from the
previously used state.
If sequence programming activation signal is lost, the sequence
programming is stopped and all timers and outputs (RO/TO/AO) are set to
zero. Sequence programming state (
SEQ PROG STATE) remains
unchanged.
If start from the first sequence programming state is required, the sequence
programming must be reset by parameter
SEQ PROG RESET. If start
from the first sequence programming state is always required, reset and start
signal sources must be through the same digital input (
and
SEQ
PROG START).
Note
: The drive will not start if no Run Enable signal is received (
RUN
ENABLE).
NOT SEL
DI1(INV)
Sequence programming activation through inverted digital input DI1.
0 = active, 1 = inactive.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
NOT SEL
No sequence programming activation signal
0
DI1
Sequence programming activation through digital input DI1. 1 = active,
0 = inactive.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
DRIVE START
Sequence programming activation at drive start
6
TIMED FUNC 1
Sequence programming is activated by time function 1. See parameter group
7
TIMED FUNC 2
See selection TIMED FUNC 1.
8
TIMED FUNC 3
See selection TIMED FUNC 1.
9
TIMED FUNC 4
See selection TIMED FUNC 1.
10
RUNNING
Sequence programming is always active.
11
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......