Actual signals and parameters
217
SEQ PROG OUT
Sequence programming output. See parameter group
33
4011
INTERNAL SETPNT
Selects a constant value as process PID controller reference, when
parameter
SET POINT SEL value is set to INTERNAL.
40
x…x
Unit and range depend on the unit and scale defined by parameters
UNITS
UNIT SCALE.
4012
SETPOINT MIN
Defines the minimum value for the selected PID reference signal source. See
parameter
0
-500.0…500.0%
Value in percent.
Example:
Analog input AI1 is selected as the PID reference source (value of
parameter
4010
is AI1). The reference minimum and maximum correspond
the
MINIMUM AI1 and
MAXIMUM AI1 settings as follows:
1 = 0.1%
4013
SETPOINT MAX
Defines the maximum value for the selected PID reference signal source.
See parameters
SETPOINT MIN.
100
-500.0…500.0%
Value in percent
1 = 0.1%
4014
FBK SEL
Selects the process actual value (feedback signal) for the process PID
controller: The sources for the variables ACT1 and ACT2 are further defined
by parameters
ACT1 INPUT and
ACT2 INPUT.
ACT1
ACT1
ACT1
1
ACT1-ACT2
Subtraction of ACT1 and ACT 2
2
ACT1+ACT2
Addition of ACT1 and ACT2
3
ACT1*ACT2
Multiplication of ACT1 and ACT2
4
ACT1/ACT2
Division of ACT1 and ACT2
5
MIN(ACT1,2)
Selects the smaller of ACT1 and ACT2
6
MAX(ACT1,2)
Selects the higher of ACT1 and ACT2
7
sqrt(ACT1-2)
Square root of the subtraction of ACT1 and ACT2
8
sqA1+sqA2
Addition of the square root of ACT1 and the square root of ACT2
9
sqrt(ACT1)
Square root of ACT1
10
COMM FBK 1
PID COMM VALUE 1 value
11
COMM FBK 2
PID COMM VALUE 2 value
12
4015
FBK MULTIPLIER
Defines an extra multiplier for the value defined by parameter
FBK SEL.
Parameter is used mainly in applications where feedback value is calculated
from a other variable (e.g. flow from pressure difference).
0
-32.768…32.767
Multiplier. If parameter value is set to zero, no multiplier is used.
1 = 0.001
4016
ACT1 INPUT
Defines the source for actual value 1 (ACT1). See also parameter
ACT1 MINIMUM.
AI2
AI1
Uses analog input 1 for ACT1
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Ref
4013
4012
1301
1302
AI1
(%)
1301
1302
Ref
(MAX)
(MIN)
4013
4012
(MAX)
(MIN)
AI1
(%)
MAX > MIN
MIN > MAX
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......