Actual signals and parameters 249
4414
DI STATUS OUTLET
NOT SEL
Selects the digital input for connection of a pressure switch at the pump/fan outlet. The
“normal” state is 1 (active). If the selected input switches to 0 (inactive), the action
defined by parameter
is taken after a delay set by
expires.
0 = NOT SEL – No digital input selected.
1 = DI1 – Pump/fan outlet pressure monitored through digital input DI1.
2 = DI2 – See selection DI1.
3 = DI3 – See selection DI1.
4 = DI4 – See selection DI1.
5 = DI5 – See selection DI1.
4415
OUTLET CTRL DLY
0.1 … 3600.0 s
1 = 0.1 s
60.0 s
Sets the delay after which the action defined by parameter
is taken on detection of high outlet pressure.
4416
OUTLET FORCED
REF
-100.0 … 100.0%
1 = 0.01%
0.0%
This reference is used after detection of high outlet pressure. See parameter
WARNING!
Make sure that it is safe to continue operation using this reference.
4417
PID OUT DEC TIME
0.0 … 3800.0 s
1 = 0.1 s
60.0 s
PI controller ramp-down time. See selection PROTECT for parameters
and
.
4418
APPL PROFILE CTL
NOT SEL
and
provide the Application profile protection feature, based on long-term monitoring
of an internal status signal. If the selected signal exceeds (and remains above) the
supervision limit for a longer time than the set delay (parameter
), the internal status signal “PROFILE HIGH” is set to 1. The signal can be directed
to a relay output (see parameter
0 = NOT SEL – Not selected.
1 = CONTROL DEV1 – Signal
is monitored and compared to
. Monitoring the deviation between the
reference and the actual value gives an indication of the general condition of the
pump, piping and valves.
2 = CONTROL DEV2 – Signal
is monitored and compared to
. Monitoring the deviation between the
reference and the actual value gives an indication of the general condition of the
pump, piping and valves.
3 = APPL OUTPUT – Signal
is monitored and compared to
. The signal constantly remaining at 100%
may indicate a leak in the output piping.
4419
PROFILE OUTP LIM
-500.0 … 500.0%
1 = 0.1%
100.0%
Supervision limit for the Application profile protection. See also description in
parameter
.
Group 44: Pump protection
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...