202 Actual signals and parameters
Group 29: Maintenance trig
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice is displayed on the control panel signals that maintenance is
due.
Group 29: Maintenance trig
Code
Description
Range
Resolution
Default
S
2901
COOLING FAN TRIG
0.0 … 6553.5 kh
0.1 kh
0.0
Defines the trigger point for the drive cooling fan run time counter. Value is compared
to parameter
• Time. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2902
COOLING FAN ACT
0.0 … 6553.5 kh
0.1 kh
0.0
Defines the actual value for the cooling fan run time counter. When parameter
has been set to a non zero value, the counter starts. When the
actual value of the counter exceeds the value defined by parameter
maintenance notice is displayed on the panel.
• Time. Parameter is reset by writing 0.0 to it.
2903
REVOLUTION TRIG
0 … 65535 MRev
1 MRev
0
Defines the trigger point for the motor revolution counter. Value is compared to
parameter
value.
• Millions of revolutions. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2904
REVOLUTION ACT
0 … 65535 MRev
1 MRev
0
Defines the actual value for the motor revolution counter. When parameter
has been set to a non zero value, the counter starts. When the
actual value of the counter exceeds the value defined by parameter
maintenance notice is displayed on the panel.
• Millions of revolutions. Parameter is reset by setting it to zero.
2905
RUN TIME TRIG
0.0 … 6553.5 kh
0.1 kh
0.0
Defines the trigger point for the drive run time counter. Value is compared to the value
of parameter
• Time. If parameter value is set to zero, the trigger is disabled.
0.0 = NOT SEL
2906
RUN TIME ACT
0.0 … 6553.5 kh
0.1 kh
0.0
Defines the actual value for the drive run time counter. When parameter
has been set to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by parameter
, a maintenance
notice is displayed on the panel.
• Time. Parameter is reset by setting it to zero.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...