![ABB ACS320 series User Manual Download Page 159](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965159.webp)
Actual signals and parameters 159
Group 04: Fault history
This group stores a recent history of the faults reported by the drive.
Group 04: Fault history
Code
Description
Range
Resolution
Default
S
0401
LAST FAULT
Fault code text
1
0
0 = Clear the fault history (on panel = NO RECORD).
n = Fault code of the last recorded fault.
• The fault code is displayed as a name. See chapter
on page
for
the fault codes and names. The fault name shown for this parameter may be shorter
than the corresponding name in the fault listing, which shows the names as they are
shown in the fault display.
0402
FAULT TIME 1
Date dd.mm.yy /
power-on days
1
0
The day on which the last fault occurred. Either as:
• A date – if real time clock is operating.
• The number of days after power on – if real time clock is not used, or was not set.
0403
FAULT TIME 2
Time hh:mm:ss
2 s
0
The time at which the last fault occurred. Either as:
• Real time, in format hh:mm:ss – if real time clock is operating.
• The time since power on (less the whole days reported in parameter
), in format hh:mm:ss – if real time clock is not used, or was not set.
Format on the basic control panel: Time elapsed after power-on in 2-second ticks
(minus the whole days stated by signal
). 30 ticks = 60 seconds.
For example, value 514 equals 17 minutes and 8 seconds (= 514/30).
0404
SPEED AT FLT
-
1 rpm
0
The motor speed (rpm) at the time the last fault occurred.
0405
FREQ AT FLT
-
0.1 Hz
0.0
The frequency (Hz) at the time the last fault occurred.
0406
VOLTAGE AT FLT
-
0.1 V
0.0
The DC bus voltage (V) at the time the last fault occurred.
0407
CURRENT AT FLT
-
0.1 A
0.0
The motor current (A) at the time the last fault occurred.
0408
TORQUE AT FLT
-
0.1%
0.0
The motor torque (%) at the time the last fault occurred.
0409
Reserved for future use
0412
PREVIOUS FAULT 1
Fault code text
1
0
Fault code of the second last fault. Read-only
0413
PREVIOUS FAULT 2
Fault code text
1
0
Fault code of the third last fault. Read-only.
0414
DI 1-5 AT FLT
Status of digital inputs DI1...5 at the time the latest fault occurred (binary).
Example:
10000 = DI1 is on, DI2...DI5 are off.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...