278 Actual signals and parameters
DI3
Enables the Interlocks function and assigns a digital input
(starting with DI3) to the interlock signal for each PFC relay.
These assignments are defined in the following table and
depend on:
• the number of PFC relays (number of parameters
])
• the Autochange function status (disabled if
= 0.0, and otherwise enabled).
3
DI4
Enables the Interlock function and assigns a digital input
(starting with DI4) to the interlock signal for each PFC relay.
These assignments are defined in the following table and
depend on:
• the number of PFC relays (number of parameters
])
• the Autochange function status (disabled if
= 0.0, and otherwise enabled).
4
All parameters
No.
Name/Value
Description
Def/FbEq
No. of
PFC
relays
Autochange disabled
Autochange enabled
0
DI1…DI2: Free
DI3: Speed reg motor
DI4…DI5: Free
Not allowed
1
DI1…DI2: Free
DI3: Speed reg motor
DI4: First PFC relay
DI5…DI5: Free
DI1…DI2: Free
DI3: First PFC relay
DI4…DI5: Free
2
DI1…DI2: Free
DI3: Speed reg motor
DI4: First PFC relay
DI5: Second PFC relay
DI1…DI2: Free
DI3: First PFC relay
DI4: Second PFC relay
DI5: Free
3
Not allowed
DI1…DI2: Free
DI3: First PFC relay
DI4: Second PFC relay
DI5: Third PFC relay
4…5 Not allowed
Not allowed
No. of
PFC
relays
Autochange disabled
(Parameter
Autochange enabled
(Parameter
)
0
DI1…DI3: Free
DI4: Speed reg motor
DI5: Free
Not allowed
1
DI1…DI3: Free
DI4: Speed reg motor
DI5: First PFC relay
DI1…DI3: Free
DI4: First PFC relay
DI5: Free
2
Not allowed
DI1…DI3: Free
DI4: First PFC relay
DI5: Second PFC relay
3…5 Not allowed
Not allowed