Actual signals and parameters 263
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
RESET
Reset loggers. Parameter is set to NOT SEL.
7
DI1(INV)
Reset loggers on the falling edge of DI1.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
6404 AL2 SIGNAL
Defines the signal logged for amplitude logger 2
103
x…x
Parameter index in group
. Eg 102 =
.
1 = 1
6405 AL2 SIGNAL
BASE
Defines the base value from which the percentage
distribution is calculated. Representation and default value
depends on the signal selected with parameter
-
-
-
-
6406 PEAK VALUE
Detected peak value of the signal selected with parameter
-
-
-
-
6407 PEAK TIME 1
Date of the peak value detection
-
0…65535 d
Day on which the peak value was detected.
Format: Date if the real time clock is operating. / The
number of days elapsed after the power-on if the real time
clock is not used, or was not set.
1 = 1 d
6408 PEAK TIME 2
Time of the peak value detection
-
00:00:00…
23:59:58
hours:minutes:seconds
1 = 2 s
6409 CURRENT AT
PEAK
Current at the moment of the peak value
-
0.0…6553.5 A
1 = 0.1 A
6410 UDC AT PEAK DC voltage at the moment of the peak value
-
0…65535 V
1 = 1 V
6411 FREQ AT
PEAK
Output frequency at the moment of the peak value
-
0.0…6553.5 Hz
1 = 0.1 Hz
6412 TIME OF
RESET 1
Last reset date of the peak logger and amplitude logger 2
-
0…65535 d
Day of the last reset.
Format: Date if the real time clock is operating. / The
number of days elapsed after the power-on if the real time
clock is not used, or was not set.
1 = 1 d
6413 TIME OF
RESET 2
Last reset time of the peak logger and amplitude logger 2
-
All parameters
No.
Name/Value
Description
Def/FbEq