Actual signals and parameters 195
1606 LOCAL LOCK
Disables entering the local control mode or selects the
source for the local control mode lock signal. When local
lock is active, entering the local control mode is disabled
(LOC/REM key of the panel).
NOT SEL
Local control is allowed.
0
DI1
Local control mode lock signal through digital input DI1.
Rising edge of digital input DI1: Local control disabled.
Falling edge of digital input DI1: Local control allowed.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
ON
Local control is disabled.
7
COMM
Fieldbus interface as the source for the local lock, ie Control
bit 14. The Control word is
sent by the fieldbus controller through the embedded
fieldbus (Modbus) to the drive. For the Control word bits,
see section
.
Note:
This setting applies only for the DCU profile.
8
DI1(INV)
Local lock through inverted digital input DI1. Rising edge of
inverted digital input DI1: Local control allowed. Falling edge
of inverted digital input DI1: Local control disabled.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
1607 PARAM SAVE
Saves the valid parameter values to the permanent
memory.
Note:
A new parameter value of a standard macro is saved
automatically when changed from the panel but not when
altered through a fieldbus connection.
DONE
Saving completed
0
SAVE...
Saving in progress
1
All parameters
No.
Name/Value
Description
Def/FbEq