Program features 131
Motor heating function
With the motor heating function, DC current can be injected into the motor to keep it
warm in low temperatures. The function can be enabled with parameter
. The source to activated the function is selected with parameter
Parameter
and the relay outputs 1...4 (parameters
...
and
) can be used to indicate the status of motor heating.
Settings
Diagnostics
Critical speeds
Critical speeds function is available for applications where it is necessary to avoid
certain motor speeds (drive output frequencies) or speed bands (output frequency
bands) because of eg mechanical resonance problems. The user can define three
critical frequencies or frequency bands.
Settings
Constant speeds
It is possible to define seven positive constant speeds. Constant speeds are selected
with digital inputs. Constant speed activation overrides the external speed reference.
Constant speed selections are ignored if
• PID reference is being followed, or
• drive is in the local control mode.
This function operates on a 2 ms time level.
Settings
Parameter
Additional information
Activates the motor heating feature
A percentage of nominal current that is to be dc injected
into the motor windings.
Defines the input that turns On/Off motor heating.
Alarm
Additional information
Motor heating active
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182