Parameters 99
05
Various run-time-type counters and measurements
related to drive maintenance.
All parameters in this group are read-only unless
otherwise noted.
Drive on-time counter. The counter runs when the
drive is powered.
-
0…65535 d
On-time counter (number of days).
1 = 1 d
Motor run-time counter. The counter runs when the
inverter modulates.
-
0…65535 d
Motor run-time counter.
1 = 1 d
Corresponding parameter to
in hours, that is, 24 *
value + fractional part of a
day.
-
0…
429496729.5 h
Hours.
1 = 1 h
Running time of the drive cooling fan. Can be reset
from the control panel by keeping Reset down for
over 3 seconds.
-
0…65535 d
Cooling fan run-time.
1 = 1 d
Measured temperature of the control board.
-
-100… 300 °C or °F
Temperature in degrees Celsius for Fahrenheit.
1 = unit
Estimated drive temperature in percent of fault limit.
The fault limit varies according to the type of the
drive.
0.0% = 0 °C (32 °F)
100.0% = Fault limit
-
-40.0…160.0%
Temperature in percent.
1 = 1%
Diagnostic word 1. For possible causes and remedies,
see chapter
0b0000
0b0000…0b1111
Diagnostic word 1.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Value
0
Any warning or fault Yes = Drive has generated a warning or tripped on a fault.
1
Any warning
Yes = Drive has generated a warning.
2
Any fault
Yes = Drive has tripped on a fault.
3
Reserved
4
Overcurrent fault
Yes = Drive has tripped on fault
5
Reserved
6
DC overvoltage
Yes = Drive has tripped on fault
.
7
DC undervoltage
Yes = Drive has tripped on fault
8
Reserved
9
Device overtemp flt Yes = Drive has tripped on fault
10...15 Reserved
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...