Fieldbus control through the embedded fieldbus interface (EFB)
375
Error code registers (holding registers 400090…400100)
These registers contain information about the last query. The error register is
cleared when a query has finished successfully.
33
Delayed status of digital
input DI2 (parameter
, bit 1)
Delayed status of digital input DI2 (parameter
, bit 1)
34
Delayed status of digital
, bit 2)
Delayed status of digital input DI3 (parameter
, bit 2)
35
Delayed status of digital
, bit 3)
Delayed status of digital input DI4 (parameter
, bit 3)
36
Delayed status of digital
input DO1 (parameter
Delayed status of digital input DO1
(parameter
, bit 4)
Reference
Name
Description
89
Reset Error Registers
1 = Reset internal error registers (91…95). 0 = Do
nothing.
90
Error Function Code
Function code of the failed query.
91
Error Code
Set when exception code 04h is generated (see
table above).
• 00h No error
• 02h Low/High limit exceeded
• 03h Faulty Index: Unavailable index of an array
parameter
• 05h Incorrect Data Type: Value does not match the
data type of the parameter
• 65h General Error: Undefined error when handling
query
92
Failed Register
The last register (discrete input, coil, input
register or holding register) that failed to be read
or written.
93
Last Register Written
Successfully
The last register (discrete input, coil, input
register or holding register) that was written
successfully.
94
Last Register Read
Successfully
The last register (discrete input, coil, input
register or holding register) that was read
successfully.
Reference
ABB Drives profile
DCU Profile
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...