Parameters 135
Supervision 4
.
27
Supervision 5
Bit 4 of
28
Supervision 6
Bit 5 of
.
29
-
, selects
the source for the activation of jogging function 1.
(Jogging function 1 can also be activated through
fieldbus regardless of parameter
1 = Jogging 1 active.
Notes:
• Jogging is supported in vector control mode only.
• If both jogging 1 and 2 are activated, the one that
was activated first has priority.
• This parameter cannot be changed while the drive
is running.
not used
Not used
0.
0
Used
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
Supervision 1
24
Supervision 2
.
25
Supervision 3
26
Supervision 4
.
27
Supervision 5
Bit 4 of
28
Supervision 6
Bit 5 of
.
29
-
, selects
the source for the activation of jogging function 2.
(Jogging function 2 can also be activated through
fieldbus regardless of parameter
1 = Jogging 2 active.
For the selections, see parameter
.
Notes:
• Jogging is supported in vector control mode only.
• If both jogging 1 and 2 are activated, the one that
was activated first has priority.
• This parameter cannot be changed while the drive
is running.
not used
Select the action to take when the drive switches
between remote and local control modes.
Keep running
The drive will continue to run when the user changes
between the local and remote control of the drive. See
Local and external control locations
0
Stop
The drive will stop when the user changes between
the local and remote control of the drive. See
and external control locations
(page
).
1
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...