Parameters 119
Defines the filter time constant for analog input AI2.
See parameter
Note: The signal is also filtered due to the signal
interface hardware (approximately 0.25 ms time
constant). This cannot be changed by any parameter.
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the
analog signal from plant is wound to its minimum
setting.
4.000 mA or
0.000 V
0.000…22.000 mA
or 0.000…11.000 V
Minimum value of AI2.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the
analog signal from plant is wound to its maximum
setting.
20.000 mA
or 10.000 V
0.000…22.000 mA
or 0.000…11.000 V
Maximum value of AI2.
1000 = 1 mA
or V
Defines the real value that corresponds to the
minimum analog input AI2 value defined by
parameter
12.27
AI2 min
. (Changing the polarity
settings of
12.29
and
12.101
can effectively invert the
analog input.)
0.000
-32768.000…
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the
maximum analog input AI2 value defined by
parameter
. See the drawing at
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
Value of analog input AI1 in percent of AI1 scaling
-
-
0.00… 100.00
AI1 value
100 = 1%
Value of analog input AI2 in percent of AI1 scaling
-
No.
Name/Value
Description
Default
FbEq 16
12.101
12.28
12.27
12.29
AI
in
(
12.21
)
AI
scaled
(
12.22
)
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...