CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
166
10.6.5 Connecting a grounding set
1. Connect the enclosure ground clamp
to the ground ball stud of the cabinet’s ground-
ing frame.
2. Use the telescopic insulating pole to connect
the busbar ground clamps
to the
ground ball studs of the busbars, and to tighten
each connection.
Connect the inner most busbar first
(10-10: 3)
,
then the middle busbar
(10-10: 4)
and then the
outer busbar
.
—
References
—
10-9 Four-way grounding
set
—
1. Telescopic insulating pole
2. Enclosure ground clamp
3. Busbar ground clamps
3
3
3
2
1