30 Control macros
Hand/Auto macro
This macro can be used when switching between two external control devices is
needed. Both have their own control and reference signals. One signal is used to
switch between these two. You can activate the macro from the
Control macros
view,
or set parameter
.
Default control connections for the Hand/Auto macro
Terminals
Descriptions
Digital I/O connections
21 24 V
Aux. +24 V DC, max 200 mA
22 DGND
Aux. voltage output common
8
DI1
Stop / Start (Hand)
9
DI2
Hand(1) / Auto(0)
10 DI3
Stop / Start (Auto)
11 DI4
Fault reset
12 DCOM
Digital input common
18 DO
Running
19 DO COM
Digital output common
20 DO SRC
Digital output auxiliary voltage
Analog I/O
14 AI1/DI5
Speed reference (Hand) (0...10V)
2)
13 AGND
Analog input circuit common
15 AI2
Speed reference (Auto) (4...20mA)
2)
16 AGND
Analog output circuit common
17 AO
Output frequency (0...20mA)
2)
23 10V
Ref. v10 V DC
24 SCREEN
Signal cable shield (screen)
Safe torque off (STO)
1
S+
Safe torque off function. Connected at
the factory. Drive starts only when both
circuits are closed.
2
SGND
3
S1
4
S2
Relay output
5
NC
No fault [Fault (-1)]
6
COM
7
NO
EIA-485 Modbus RTU
25 B+
Embedded Modbus RTU (EIA-485)
26 A-
27 AGND
28 SHIELD
Termination
NRKP
0D[RKP
1)