Parameters 277
Pass codes can be entered into this parameter to activate
further access levels, for example additional parameters,
parameter lock, etc. See parameter
.
Entering “358” toggles the parameter lock, which prevents
the changing of all other parameters through the control
panel or the Drive composer PC tool.
Entering the user pass code (by default, “10000000”)
enables parameters
96.102
, which can be used
to define a new user pass code and to select the actions
that are to be prevented.
Entering an invalid pass code will close the user lock if
open, ie. hide parameters
…
96.102
. After entering
the code, check that the parameters are in fact hidden.
Note:
We recommend that you change the default user
pass code.
See also section
0
0…99999999
Pass code.
-
Shows which access levels have been activated by pass
codes entered into parameter
.
0b0000
0b0000...0b1111
Active access levels.
-
Selects the control macro. See chapter
for
more information.
After a selection is made, the parameter reverts
automatically to
.
Note: When you change the default parameter values of a
macro, the new settings become valid immediately and
stay valid even if the power of the drive is switched off and
on. However, backup of the default parameter settings
(factory settings) of each standard macro is still available.
Done
Macro selection complete; normal operation.
0
ABB standard
. For scalar motor control.
1
Hand/Auto
Hand/Auto macro.
2
Hand/PID
Hand/PID macro.
3
Modbus RTU
Modbus RTU
5
Alternate
12
Motor potentiometer
13
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
0
End user
1
Service
2, 3
Reserved
4
Long menu
5...10
Reserved
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved
ACS180 FW.book Page 277 Tuesday, March 9, 2021 2:25 PM