
Notes
Wiring method
Free air
Prefer symmetrical shielded VFD cable.
Enclosures, air handlers, etc.
Allowed internally in enclosures when in ac-
cordance with UL.
1) Metallic conduit may be used as an additional ground path, provided this path is a solid path capable
of handling ground currents.
2) See NFPA NFPA 70 (NEC), UL, and local codes for your application.
3) Non-metallic conduit use underground is allowed; however, these installations inherently have an
increased chance for nuisance problems due to the potential for water/moisture in the conduit.
Water/moisture in the conduit increases the likelihood of VFD faults or warnings. Proper installation
is required to make sure there is no intrusion of water/moisture.
Metal conduit
Couple separate parts of a metal conduit together: bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Also bond the conduits
to the drive enclosure and motor frame. Use separate conduits for input power,
motor, brake resistor, and control wiring. Do not run motor wiring from more than
one drive in the same conduit.
■
Power cable shield
If the cable shield is used as the sole protective earth (PE) conductor, make sure
that its conductivity agrees with the PE conductor requirements.
To effectively suppress radiated and conducted radio-frequency emissions, the
cable shield conductivity must be at least 1/10 of the phase conductor conductivity.
The requirements are easily met with a copper or aluminum shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of
a concentric layer of copper wires with an open helix of copper tape or copper
wire. The better and tighter the shield, the lower the emission level and bearing
currents.
Guidelines for planning the electrical installation 49
Summary of Contents for ACS180-04S-03A7-1
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 24: ...24...
Page 84: ...84...
Page 96: ...96...
Page 146: ...146...
Page 148: ...Frame R0 148 Dimension drawings...
Page 149: ...Frame R1 Dimension drawings 149...
Page 151: ...Frame R3 Dimension drawings 151...
Page 152: ...Frame R4 152 Dimension drawings...
Page 160: ...160...
Page 180: ...Declarations of conformity 180 The Safe torque off function...
Page 181: ...The Safe torque off function 181...
Page 182: ...182 The Safe torque off function...
Page 183: ...The Safe torque off function 183...
Page 184: ...184...
Page 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Page 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...