background image

Related documents

 3AXD50000625970 Rev A EN 2020-04-21

© Copyright 2020 ABB. All rights reserved.

ACS150 user’s manual

3AFE68576032

ACS150 manual list

9AKK107680A5637

POWER-UP

Apply input power. 

The panel powers up into the Output mode.

 

ENTRY OF START-UP DATA

Select the application macro (parameter 

9902

 ) 

according to how the control cables are 

connected. The default value 1 (ABB STANDARD) 

is suitable in most cases.

The general parameter setting procedure in the 

Short parameter mode is described below. 
1. To go to the Main menu, press 

 if the 

bottom line shows OUTPUT; otherwise press 

 repeatedly until you see MENU at the 

bottom.

2. Press keys 

/

 until you see 

“PAr S” on the display.

 

3. Press 

. The display shows a parameter 

of the Short parameter mode.

4.Find the appropriate parameter with keys 

/

.

5.Press and hold 

 for about two seconds 

until the parameter value is shown with 

 

under the value.

6.Change the value with keys 

/

. The value changes faster while you 

keep the key pressed down.

 

7. Save the parameter value by pressing 

.

 

Enter the motor data from the motor nameplate.

• motor nominal voltage (

9905)

• motor nominal current (

9906)

• motor nominal frequency (

9907)

Set the maximum value for external reference 

REF1 (

1105).

Set constant speeds 1, 2 and 3 (

1202, 1203, 1204).

Set the minimum value (%) corresponding to the 

minimum signal for AI(1) (

1301). Typical settings:

0% for 0…20 mA (or 0…10 V) signal

20% for 4…20 mA (or 2…10 V) signal

Set the maximum limit for the drive output 

frequency (

2008). This is equal to power line 

frequency, typically. That is: 50 or 60 Hz.

 

Select the motor stop function (

2102).

1 = Stop by cutting off the motor power supply. 

Motor coasts to stop.

2 = Stop along ramp defined by parameter.

DIRECTION OF THE MOTOR ROTATION

Check the direction of the motor rotation.

 

1. Turn the potentiometer fully 

counterclockwise.

2. If the drive is in remote control (REM shown on 

the left), switch to local control by pressing 

3. Press 

 to start the motor.

4.Turn the potentiometer slightly clockwise until 

the motor rotates.

5.Check that the actual direction of the motor is 

the same as indicated on the display (FWD 

means forward and REV reverse).

6.Press 

 to stop the motor.

To change the direction of the motor rotation:

1. Disconnect input power from the drive, and 

wait 5 minutes for the intermediate circuit 

capacitors to discharge. Lock out and tag out. 

Measure the voltage between each input 

terminal (U1, V1 and W1) and earth with a 

multimeter to ensure that the drive is 

discharged.

2. Exchange the position of two motor cable 

phase conductors at the drive output 

terminals or at the motor connection box.

3. Verify your work by applying input power and 

repeating the check as described above.

ACCELERATION/DECELERATION TIMES

Set the acceleration time 1 (

2202) and 

deceleration time 1 (

2203).

FINAL CHECK

The start-up is now completed. If you want to 

save your setting as a user macro, scroll to 

Parameter 9902 and select value -1 (USER S1 

SAVE).

Check that there are no faults or alarms shown 

on the display. 

The drive is now ready for use.

LOC

     Hz

OUTPUT

 FWD

00

.

LOC

S

     

PAR

   FWD

9902

LOC

     

MENU

 

  FWD

rEF

LOC

     

MENU

 

  FWD

PAr S

LOC

S

     

 PAR

  FWD

9902

LOC

S

     

 PAR

  FWD

9907

SET

LOC

     

           Hz 
 PAR 

SET

 FWD

500

.

LOC

     

           Hz 
 PAR 

SET

 FWD

600

.

LOC

S

     

 PAR

  FWD

9907

LOC

S

     

 PAR

  FWD

9905

LOC

S

     

 PAR

  FWD

1105

LOC

S

     

 PAR

  FWD

1202

LOC

S

     

 PAR

  FWD

1301

LOC

S

     

 PAR

  FWD

2008

LOC

S

     

 PAR

  FWD

2102

LOC

S

     

 PAR

  FWD

1202

forward

reverse

LOC

REM

LOC

S

     

 PAR

  FWD

2202

LOC

S

     

 PAR

  FWD

9902

Fault codes

This is a short list of fault messages. 

Ratings   

Fuses and typical power cable sizes

The table list the fuses for protection against short-circuits in the input power 

cable or drive. The table also shows typical power cable sizes.

 

Ambient conditions

Dimensions and weights

Fault

Description

F0001

OVERCURRENT - Output current has exceeded trip level.

F0002

DC OVERVOLT - Excessive intermediate circuit DC voltage.

F0003

DEV OVERTEMP - Drive IGBT temperature is excessive.

F0004

SHORT CIRC - Short-circuit in motor cable(s) or motor.

F0006

DC UNDERVOLT - Intermediate circuit DC voltage is not sufficient.

F0009

MOT OVERTEMP - Motor temperature estimation is too high.

F0016

EARTH FAULT - Drive has detected earth (ground) fault in motor or motor cable.

F0022

INPUT PHASE LOSS - Intermediate circuit DC voltage is oscillating due to 

missing input power line phase or blown fuse.

ACS150-

Input

Output

Frame

size

I

1N

I

1N 

(480 V)

I

2N

I

2,1/10

I

2max

P

N

x = E/U

1)

A

A

A

A

A

kW

hp

1-phase 

U

N

 = 230 V (200…240 V)

01x-02A4-2

6.1

-

2.4

3.6

4.2

0.37

0.5

R0

01x-04A7-2

11.4

-

4.7

7.1

8.2

0.75

1

R1

01x-06A7-2

16.1

-

6.7

10.1

11.7

1.1

1.5

R1

01x-07A5-2

16.8

-

7.5

11.3

13.1

1.5

2

R2

01x-09A8-2

21.0

-

9.8

14.7

17.2

2.2

3

R2

3-phase 

U

N

 = 230 V (200…240 V)

03x-02A4-2

4.3

-

2.4

3.6

4.2

0.37

0.5

R0

03x-03A5-2

6.1

-

3.5

5.3

6.1

0.55

0.75

R0

03x-04A7-2

7.6

-

4.7

7.1

8.2

0.75

1

R1

03x-06A7-2

11.8

-

6.7

10.1

11.7

1.1

1.5

R1

03x-07A5-2

12.0

-

7.5

11.3

13.1

1.5

2

R1

03x-09A8-2

14.3

-

9.8

14.7

17.2

2.2

3

R2

3-phase 

U

N

 = 400/480 V (380…480 V)

03x-01A2-4

2.2

1.8

1.2

1.8

2.1

0.37

0.5

R0

03x-01A9-4

3.6

3.0

1.9

2.9

3.3

0.55

0.75

R0

03x-02A4-4

4.1

3.4

2.4

3.6

4.2

0.75

1

R1

03x-03A3-4

6.0

5.0

3.3

5.0

5.8

1.1

1.5

R1

03x-04A1-4

6.9

5.8

4.1

6.2

7.2

1.5

2

R1

03x-05A6-4

9.6

8.0

5.6

8.4

9.8

2.2

3

R1

03x-07A3-4

11.6

9.7

7.3

11.0

12.8

3

4

R1

03x-08A8-4

13.6

11.3

8.8

13.2

15.4

4

5

R1

00353783.xls J

I

1N

continuous rms input current (for dimensioning cables and fuses)

I

1N

 (480 V) continuous rms input current (for dimensioning cables and fuses) for drives with 

480 V input voltage

I

2N

continuous rms current. 50% overload is allowed for one minute every ten 

minutes.

I

2,1/10

maximum (50% overload) current allowed for one minute every ten minutes

I

2max

maximum output current. Available for two seconds at start, otherwise as long 

as allowed by the drive temperature.

P

N

typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The 

horsepower ratings apply to most NEMA 4-pole motors. 

ACS150-…x 

= E/U

Fuses

Size of CU conductor in cablings

 gG

UL 

Class T 

(600 V)

Supply

(U1, V1, W1)

Motor 

(U2, V2, W2)

PE

Brake

(BRK+ and 

BRK-)

A

A

mm

2

AWG

mm

2

AWG

mm

2

AWG

mm

2

AWG

1-phase 

U

N

 = 230 V (200…240 V)

01x-02A4-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

01x-04A7-2

16

20

2.5

14

0.75

18

2.5

14

2.5

14

01x-06A7-2 16/20 

1)

25

2.5

10

1.5

14

2.5

10

2.5

12

01x-07A5-2 20/25 

1)

30

2.5

10

1.5

14

2.5

10

2.5

12

01x-09A8-2 25/35 

1)

35

6

10

2.5

12

6

10

6

12

3-phase 

U

N

 = 230 V (200…240 V)

03x-02A4-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-03A5-2

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-04A7-2

10

15

2.5

14

0.75

18

2.5

14

2.5

14

03x-06A7-2

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-07A5-2

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-09A8-2

16

20

2.5

12

2.5

12

2.5

12

2.5

12

3-phase 

U

N

 = 400/480 V (380…480 V)

03x-01A2-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-01A9-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-02A4-4

10

10

2.5

14

0.75

18

2.5

14

2.5

14

03x-03A3-4

10

10

2.5

12

0.75

18

2.5

12

2.5

12

03x-04A1-4

16

15

2.5

12

0.75

18

2.5

12

2.5

12

03x-05A6-4

16

15

2.5

12

1.5

14

2.5

12

2.5

12

03x-07A3-4

16

20

2.5

12

1.5

14

2.5

12

2.5

12

03x-08A8-4

20

25

2.5

12

2.5

12

2.5

12

2.5

12

00353783.xls J

1)

 If 50% overload capacity is needed, use the larger fuse alternative.

Requirement

During operation (installed for stationary use)

Installation altitude

0…2000 m (0…6562 ft) above sea level (with output derating 

above 1000 m [3281 ft])

Surrounding air 

temperature

-10…+50 °C (14…122 °F). If the temperature is more than 40 °C 

(104 °F), output derating is necessary. No frost permitted.

Relative humidity

0…95% without condensation

Contamination levels

(IEC 60721-3-3: 2002)

No conductive dust permitted

Shock (IEC 60068-2-27, 

ISTA 1A)

Not permitted

Free fall

Not permitted

IP20 (cabinet) / UL open

Frame 

size

H1

H2

H3

W

D

Weight

mm

in

mm

in

mm

in

mm

in

mm

in

kg

lb

R0

169

6.65

202

7.95

239

9.41

70

2.76

142 5.59

1.1

2.4

R1

169

6.65

202

7.95

239

9.41

70

2.76

142 5.59 1.3/1.2

1)

2.9/2.6

1)

R2

169

6.65

202

7.95

239

9.41

105

4.13

142 5.59

1.5

3.3

IP20 / NEMA 1

Frame 

size

H4

H5

W

D

-

Weight

mm

in

mm

in

mm

in

mm

in

-

-

kg

lb

R0

257 10.12 280 11.02

70

2.76

142

5.59

-

-

1.5

3.3

R1

257 10.12 280 11.02

70

2.76

142

5.59

-

-

1.7/1.6

1)

3.7/3.5

1)

R2

257 10.12 282 11.10 105

4.13

142

5.59

-

-

1.9

4.2

3AXD00000353783 L

1)

200 V unit weight / 400 V unit weight

IP20 (cabinet) / UL open

H1

height without fastenings or clamping plate

H2 height with fastening and without clamping plate

H3 height with fastenings and clamping plate

W

width

D

depth

IP20 / NEMA 1 (drive with optional MUL-xx kit installed)

H4 height with fastenings and connection box

H5 height with fastenings, connection box and hood

Free space requirements

Markings

The applicable markings are shown on the type designation label

Above

Below

Sides

mm

in

mm

in

mm

in

75

3

75

3

0

0

3AXD00000353783 L

CE

UL RCM EAC

WEEE EIP

„

Reviews: