PREVENTIVE AND CORRECTIVE MAINTENANCE
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
146/166
11.4. Removing the CDP control panel
IMPORTANT!
If the CDP control panel is removed during operation, the drive can
only be stopped by pressing the
EMERGENCY OFF
button.
1.
If the panel is removed while the drive is in operation, check the setting of
parameter
31.06 PANEL LOSS SUPERVISION
first.
If the parameter is set to
NOT USED
, the panel can be removed without
interrupting drive operation.
For information on setting parameters, see
“Appendix G
-
Signal and parameter table”.
2.
Proceed as illustrated.
The green LED (4) signals that the control voltage has been switched on.
1
2
3
4