7.7.2. Connecting the cables
7.7.2.1. IOEC modules
–
Connect the cables for digital and analog input and output signals to the
distribution terminals.
7.7.2.2. Conductors
–
If a twisted pair cable is used, leave the unshielded cable ends twisted until
they reach the terminals.
–
Leave unshielded conductor ends as short as possible (not longer than 50 mm).
7.7.2.3. Cable shields
–
Connect the shield of serial communications cables to the fieldbus adapter.
–
Connect the overall shield and the individual shields of the encoder cable to the
separate shield grounding bracket (2 in Fig. 7
22)
IMPORTANT!
DO NOT connect the shields directly to the encoder adapter
(1 in Fig. 7
22).
NOTE – To accommodate encoder cables of different diameters, ground
clamps (3 in Fig. 7
22) of different sizes are supplied.
Figure 7
-
22 Shield grounding point for encoder cable
1.
Encoder adapter
2.
Shield ground bracket
3.
Grounding clamp
1
2
3