Fault tracing
284
LOAD SP DW LIM
(FFB9)
3.32 CSW bit 6
The speed reference is limited in the reverse
direction according to the Load speed control
function.
Check motor current settings and group 77
settings.
MACRO CHANGE
(FF69)
Macro is restoring or user macro is being
saved.
Wait until drive has finished task.
MASTERLIM/FLT
(FFB2)
Master drive has gone into a fault or has hit
any of the limits. This message is displayed in
the Follower drives only
See Master drive for more detailed description
of fault of limit.
MOT CUR LIM
(2300)
3.18 AW 5 bit 10
(programmable
Fault Function
Drive limits motor current according to current
limit defined with parameter
MAXIMUM
CURRENT.
Reduce load or increase ramp time.
Increase parameter
MAXIMUM
CURRENT value.
Check Fault Function parameters.
MOTOR STALL
(7121)
3.09 AW 2 bit 9
(programmable
Fault Function
Motor is operating in stall region due to, for
example, excessive load or insufficient motor
power.
Check motor load and drive ratings.
Check Fault Function parameters.
MOTOR STARTS
(FF34)
Motor identification run starts. This warning
belongs to ID run procedure.
Wait until drive indicates that motor
identification is completed.
MOTOR TEMP
(4310)
3.08 AW 1 bit 3
(programmable
Fault Function
)
Motor temperature is too high (or appears to be
too high) due to excessive load, insufficient
motor power, inadequate cooling or incorrect
start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check Fault Function parameters.
MOTOR 1 TEMP
(4312)
3.16 AW 4 bit 1
Measured motor temperature has exceeded
alarm limit set with parameter
Check value of alarm limit.
Check that actual number of sensors
corresponds to value set with parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP
(4313)
3.16 AW 4 bit 2
Measured motor temperature has exceeded
alarm limit set with parameter
Check value of alarm limit.
Check that actual number of sensors
corresponds to value set with parameter.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
WARNING
CAUSE
WHAT TO DO
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...