![ABB ACQ810 Hardware Manual Download Page 53](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066053.webp)
Planning the electrical installation 53
5. Ensure that the motor insulation system withstands the maximum peak voltage in the
below for the required motor insulation
system and drive filtering.
Example:
When the supply voltage is 440 V, the maximum peak voltage in the motor
terminals can be approximated as follows: 440 V · 1.35 · 2 = 1190 V. Check that the
motor insulation system withstands this voltage.
6. Use insulated N-end (non-drive end) bearings and output filters from ABB according to
the
below.
Requirements table
The following table shows how to select the motor insulation system and when an optional
ABB du/dt filter, insulated N-end (non-drive end) motor bearings and ABB common mode
filters are required. Failure of the motor to fulfil the following requirements or improper
installation may shorten motor life or damage the motor bearings and voids the warranty.
Note:
The drive is equipped with the common mode filter as standard.
Motor
type
Nominal AC line
voltage
Requirement for
Motor
insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size > IEC 315
P
N
> 350 kW
or
frame size > IEC 400
P
N
< 134 hp
and frame size <
NEMA 500
134 hp <
P
N
< 469 hp
or frame size >
NEMA 500
P
N
> 469 hp
or frame size >
NEMA 580
ABB motors
Random-
wound
M2_ and
M3_
U
N
< 500 V
Standard
-
+ N
+ N + CMF
500 V <
U
N
< 600 V Standard
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
or
Reinforced
-
+ N
+ N + CMF
600 V <
U
N
< 690 V Reinforced
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
Form-
wound
HX_ and
AM_
380 V <
U
N
< 690 V Standard
n.a.
+ N + CMF
P
N
< 500 kW: + N +
CMF
P
N
> 500 kW: + N +
CMF + du/dt
Old* form-
wound
HX_ and
modular
380 V <
U
N
< 690 V Check with
the motor
manufacturer.
+ du/dt with voltages over 500 V + N + CMF
Random-
wound
HX_ and
AM_ **
0 V <
U
N
< 500 V
Enamelled
wire with fiber
glass taping
+ N + CMF
500 V <
U
N
< 690 V
+ du/dt + N + CMF
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...