182 Parameters
23.15
PI adapt max sp
Maximum actual speed for speed controller adaptation.
Speed controller gain and integration time can be adapted
according to actual speed. This is done by multiplying the
gain (
) and integration time (
) by coefficients at certain speeds. The
coefficients are defined individually for both gain and
integration time.
When the actual speed is below or equal to
are
multiplied by
and
respectively.
When the actual speed is equal to or exceeds
, no adaptation takes place; in other words,
and
are used as such.
Between
the coefficients are calculated linearly on the basis of the
breakpoints.
0 … 30000 rpm
Maximum actual speed for speed controller adaptation.
1 = 1 rpm
23.16
PI adapt min sp
Minimum actual speed for speed controller adaptation. See
parameter
0 … 30000 rpm
Minimum actual speed for speed controller adaptation.
1 = 1 rpm
23.17
Pcoef at min sp
Proportional gain coefficient at minimum actual speed. See
parameter
0.000 … 10.000
Proportional gain coefficient at minimum actual speed.
1000 = 1
23.18
Icoef at min sp
Integration time coefficient at minimum actual speed. See
parameter
0.000 … 10.000
Integration time coefficient at minimum actual speed.
1000 = 1
No.
Name/Value
Description
FbEq
Coefficient for K
p
or
T
I
K
p
= Proportional gain
T
I
= Integration time
Actual speed
(rpm)
or
1.000
0
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...