Parameters 179
23.05
Acc comp DerTime
Defines the derivation time for acceleration/(deceleration)
compensation. In order to compensate inertia during
acceleration, a derivative of the reference is added to the
output of the speed controller. The principle of a derivative
action is described for parameter
Note:
As a general rule, set this parameter to a value
between 50 and 100% of the sum of the mechanical time
constants of the motor and the driven machine.
The figure below shows the speed responses when a high
inertia load is accelerated along a ramp.
No acceleration compensation:
Acceleration compensation:
0.00 … 600.00 s
Acceleration compensation derivation time.
100 = 1 s
23.06
Acc comp Ftime
Defines the derivation filter time constant for the
acceleration(/deceleration) compensation. See parameters
and
0.0 … 1000.0 ms
Derivation filter time constant for acceleration compensation. 10 = 1 ms
23.07
Speed err Ftime
Defines the time constant of the speed error low pass filter.
If the used speed reference changes rapidly, the possible
interferences in the speed measurement can be filtered with
the speed error filter. Reducing the ripple with filter may
cause speed controller tuning problems. A long filter time
constant and fast acceleration time contradict one another. A
very long filter time results in unstable control.
0.0 … 1000.0 ms
Speed error filtering time constant. 0 = filtering disabled.
10 = 1 ms
No.
Name/Value
Description
FbEq
Time
%
Speed reference
Actual speed
Time
%
Speed reference
Actual speed
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...