164 Parameters
16
16 System
Local lock and parameter lock settings; parameter restore;
user parameter set load/save; parameter change log reset;
parameter list settings; unit of power selection; application
macro display.
16.01
Local lock
Selects the source for disabling local control (Take/Release
button in the PC tool, LOC/REM key of the panel).
0 = Local control enabled.
1 = Local control disabled.
WARNING!
Before activating, ensure that the control
panel is not needed for stopping the drive!
Const
Bit pointer setting (see
on page
).
-
Pointer
16.02
Parameter lock
Selects the state of the parameter lock. The lock prevents
parameter changing.
Locked
Locked. Parameter values cannot be changed from the
control panel. The lock can be opened by entering the valid
code into parameter
.
0
Open
The lock is open. Parameter values can be changed.
1
Not saved
The lock is open. Parameter values can be changed, but the
changes will not be stored at power switch-off.
2
16.03
Pass code
Selects the pass code for the parameter lock (see parameter
).
After entering 358 at this parameter, parameter
can be adjusted. The value reverts back to 0
automatically.
0 … 2147483647
Pass code for parameter lock.
1 = 1
16.04
Param restore
Restores the original settings of the application, i.e.
parameter factory default values.
Note:
This parameter cannot be changed while the drive is
running.
Done
Restoring is completed.
0
Restore defs
All parameter values are restored to default values, except
motor data, ID run results, and fieldbus adapter and drive-to-
drive link configuration data.
1
Clear all
All parameter values are restored to default values, including
motor data, ID run results, and fieldbus adapter and drive-to-
drive link configuration data. PC tool communication is
interrupted during the restoring. Drive CPU is re-booted after
the restoring is completed.
2
16.07
Param save
Saves the valid parameter values to the permanent memory.
Note:
A new parameter value is saved automatically when
changed from the PC tool or panel but not when altered
through a fieldbus adapter connection.
Done
Save completed.
0
Save
Save in progress.
1
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...